Default:<br />
Range:<br />
Depend on:<br />
0 rpm<br />
- 4x Sync. Speed to 4x Sync.<br />
Communication information<br />
4xmotor sync speed, 1500 rpm for 1470<br />
rpm motor.<br />
Vector Brake [33G]<br />
Braking by increasing the internal electrical losses in<br />
the motor.<br />
33G Vector Brake<br />
Stp A<br />
Off<br />
Modbus Instance no/DeviceNet no: 43113<br />
Profibus slot/index 169/17<br />
Fieldbus format<br />
Int, 1=1 rpm<br />
Modbus format<br />
Int, 1=1 rpm<br />
Default:<br />
Off 0<br />
On 1<br />
Off<br />
Vector brake switched off. VSD brakes normal<br />
with voltage limit on the DC link.<br />
Maximum VSD current (I CL ) is available for<br />
braking.<br />
Brake Engage Time [33E]<br />
The brake engage time is the time the load is held to<br />
engage a mechanical brake.<br />
Default:<br />
Range:<br />
0.00 s<br />
0.00–3.00 s<br />
Communication information<br />
33E Brk Engage<br />
Stp 0.00s<br />
A<br />
Modbus Instance no/DeviceNet no: 43114<br />
Profibus slot/index 169/18<br />
Fieldbus format<br />
Long, 1=0.01 s<br />
Modbus format<br />
EInt<br />
Communication information<br />
Modbus Instance no/DeviceNet no: 43116<br />
Profibus slot/index 169/20<br />
Fieldbus format<br />
Modbus format<br />
Brake Fault trip time [33H]<br />
Default: 1.00s<br />
Range 0.00 - 5.00s<br />
UInt<br />
UInt<br />
33H Brk Fault<br />
Stp 1.00s<br />
A<br />
Wait Before Brake Time [33F]<br />
The brake wait time is the time to keep brake open<br />
and to hold the load, either in order to be able to<br />
speed up immediately, or to stop and engage the<br />
brake.<br />
33F Brk Wait<br />
Stp 0.00s<br />
A<br />
Note! The Brake Fault trip time should be set to longer<br />
time than the Brake release time[33C].<br />
The “Brake not engaged” warning is using the setting<br />
of parameter “Brake Engaged time [33E]”.<br />
Following Figure shows principle of brake operation for<br />
fault during run (left) and during stop (right)<br />
Default:<br />
Range:<br />
0.00 s<br />
0.00–30.0 s<br />
Communication information<br />
Modbus Instance no/DeviceNet no: 43115<br />
Profibus slot/index 169/19<br />
Fieldbus format<br />
Modbus format<br />
Long, 1=0.01 s<br />
EInt<br />
92 Functional Description Omron SX inverter manual