Default:<br />

Range:<br />

Depend on:<br />

0 rpm<br />

- 4x Sync. Speed to 4x Sync.<br />

Communication information<br />

4xmotor sync speed, 1500 rpm for 1470<br />

rpm motor.<br />

Vector Brake [33G]<br />

Braking by increasing the internal electrical losses in<br />

the motor.<br />

33G Vector Brake<br />

Stp A<br />

Off<br />

Modbus Instance no/DeviceNet no: 43113<br />

Profibus slot/index 169/17<br />

Fieldbus format<br />

Int, 1=1 rpm<br />

Modbus format<br />

Int, 1=1 rpm<br />

Default:<br />

Off 0<br />

On 1<br />

Off<br />

Vector brake switched off. VSD brakes normal<br />

with voltage limit on the DC link.<br />

Maximum VSD current (I CL ) is available for<br />

braking.<br />

Brake Engage Time [33E]<br />

The brake engage time is the time the load is held to<br />

engage a mechanical brake.<br />

Default:<br />

Range:<br />

0.00 s<br />

0.00–3.00 s<br />

Communication information<br />

33E Brk Engage<br />

Stp 0.00s<br />

A<br />

Modbus Instance no/DeviceNet no: 43114<br />

Profibus slot/index 169/18<br />

Fieldbus format<br />

Long, 1=0.01 s<br />

Modbus format<br />

EInt<br />

Communication information<br />

Modbus Instance no/DeviceNet no: 43116<br />

Profibus slot/index 169/20<br />

Fieldbus format<br />

Modbus format<br />

Brake Fault trip time [33H]<br />

Default: 1.00s<br />

Range 0.00 - 5.00s<br />

UInt<br />

UInt<br />

33H Brk Fault<br />

Stp 1.00s<br />

A<br />

Wait Before Brake Time [33F]<br />

The brake wait time is the time to keep brake open<br />

and to hold the load, either in order to be able to<br />

speed up immediately, or to stop and engage the<br />

brake.<br />

33F Brk Wait<br />

Stp 0.00s<br />

A<br />

Note! The Brake Fault trip time should be set to longer<br />

time than the Brake release time[33C].<br />

The “Brake not engaged” warning is using the setting<br />

of parameter “Brake Engaged time [33E]”.<br />

Following Figure shows principle of brake operation for<br />

fault during run (left) and during stop (right)<br />

Default:<br />

Range:<br />

0.00 s<br />

0.00–30.0 s<br />

Communication information<br />

Modbus Instance no/DeviceNet no: 43115<br />

Profibus slot/index 169/19<br />

Fieldbus format<br />

Modbus format<br />

Long, 1=0.01 s<br />

EInt<br />

92 Functional Description Omron SX inverter manual