USER’S MANUAL
Omron SX inverter manual
Omron SX inverter manual
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
No.<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
The reference signal passes the Level HI value from<br />
above (negative edge), the comparator CA1 does not<br />
change, output stays high.<br />
The reference signal passes the Level LO value from<br />
above (negative edge), the comparator CA1 is reset,<br />
output is set low.<br />
The reference signal passes the Level LO value from<br />
below (positive edge), the comparator CA1 does not<br />
change, output stays low.<br />
The reference signal passes the Level HI value from<br />
below (positive edge), the comparator CA1 output is<br />
set high.<br />
The reference signal passes the Level HI value from<br />
above (negative edge), the comparator CA1 does not<br />
change, output stays high.<br />
The reference signal passes the Level LO value from<br />
above (negative edge), the comparator CA1 is reset,<br />
output is set low.<br />
Analogue Comparator 1 Level Low<br />
[613]<br />
Selects the analogue comparator constant low level<br />
according to the selected value in menu [611].<br />
For default value see selection table for menu [612].<br />
Default:<br />
Range:<br />
200 rpm<br />
Communication information<br />
Enter a value for the low level.<br />
Modbus Instance no/DeviceNet no: 43403<br />
Profibus slot/index 170/52<br />
Fieldbus format<br />
Modbus format<br />
Description<br />
613 CA1 Level LO<br />
Stp A 200rpm<br />
Long,<br />
1=1 W, 0.1 A, 0.1 V,<br />
0.1 Hz, 0.1C, 1 kWh,<br />
1H, 1%, 1 rpm or 0.001<br />
via process value<br />
EInt<br />
Analogue Comparator 2 Value [614]<br />
Function is identical to analogue comparator 1 value.<br />
Default:<br />
Torque<br />
Selections: Same as in menu [611]<br />
Communication information<br />
Modbus Instance no/DeviceNet no: 43404<br />
Profibus slot/index 170/53<br />
Fieldbus format<br />
Modbus format<br />
Analogue Comparator 2 Level High<br />
[615]<br />
Function is identical to analogue comparator 1 level<br />
high.<br />
Default: 20%<br />
Range:<br />
Communication information<br />
UInt<br />
UInt<br />
Enter a value for the high level.<br />
Modbus Instance no/DeviceNet no: 43405<br />
Profibus slot/index 170/54<br />
Fieldbus format<br />
Modbus format<br />
614 CA2 Value<br />
Stp A Torque<br />
615 CA2 Level HI<br />
Stp 20%<br />
A<br />
Long<br />
1=1 W, 0.1 A, 0.1 V,<br />
0.1 Hz, 0.1C, 1 kWh,<br />
1H, 1%, 1 rpm or 0.001<br />
via process value<br />
EInt<br />
Analogue Comparator 2 Level Low<br />
[616]<br />
Function is identical to analogue comparator 1 level<br />
low.<br />
Default: 10%<br />
616 CA2 Level LO<br />
Stp 10%<br />
A<br />
Range:<br />
Enter a value for the low level.<br />
Omron SX inverter manual Functional Description 133