No.<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

The reference signal passes the Level HI value from<br />

above (negative edge), the comparator CA1 does not<br />

change, output stays high.<br />

The reference signal passes the Level LO value from<br />

above (negative edge), the comparator CA1 is reset,<br />

output is set low.<br />

The reference signal passes the Level LO value from<br />

below (positive edge), the comparator CA1 does not<br />

change, output stays low.<br />

The reference signal passes the Level HI value from<br />

below (positive edge), the comparator CA1 output is<br />

set high.<br />

The reference signal passes the Level HI value from<br />

above (negative edge), the comparator CA1 does not<br />

change, output stays high.<br />

The reference signal passes the Level LO value from<br />

above (negative edge), the comparator CA1 is reset,<br />

output is set low.<br />

Analogue Comparator 1 Level Low<br />

[613]<br />

Selects the analogue comparator constant low level<br />

according to the selected value in menu [611].<br />

For default value see selection table for menu [612].<br />

Default:<br />

Range:<br />

200 rpm<br />

Communication information<br />

Enter a value for the low level.<br />

Modbus Instance no/DeviceNet no: 43403<br />

Profibus slot/index 170/52<br />

Fieldbus format<br />

Modbus format<br />

Description<br />

613 CA1 Level LO<br />

Stp A 200rpm<br />

Long,<br />

1=1 W, 0.1 A, 0.1 V,<br />

0.1 Hz, 0.1C, 1 kWh,<br />

1H, 1%, 1 rpm or 0.001<br />

via process value<br />

EInt<br />

Analogue Comparator 2 Value [614]<br />

Function is identical to analogue comparator 1 value.<br />

Default:<br />

Torque<br />

Selections: Same as in menu [611]<br />

Communication information<br />

Modbus Instance no/DeviceNet no: 43404<br />

Profibus slot/index 170/53<br />

Fieldbus format<br />

Modbus format<br />

Analogue Comparator 2 Level High<br />

[615]<br />

Function is identical to analogue comparator 1 level<br />

high.<br />

Default: 20%<br />

Range:<br />

Communication information<br />

UInt<br />

UInt<br />

Enter a value for the high level.<br />

Modbus Instance no/DeviceNet no: 43405<br />

Profibus slot/index 170/54<br />

Fieldbus format<br />

Modbus format<br />

614 CA2 Value<br />

Stp A Torque<br />

615 CA2 Level HI<br />

Stp 20%<br />

A<br />

Long<br />

1=1 W, 0.1 A, 0.1 V,<br />

0.1 Hz, 0.1C, 1 kWh,<br />

1H, 1%, 1 rpm or 0.001<br />

via process value<br />

EInt<br />

Analogue Comparator 2 Level Low<br />

[616]<br />

Function is identical to analogue comparator 1 level<br />

low.<br />

Default: 10%<br />

616 CA2 Level LO<br />

Stp 10%<br />

A<br />

Range:<br />

Enter a value for the low level.<br />

Omron SX inverter manual Functional Description 133