14.7.2 Fuses and cable dimensions<br />

according NEMA ratings<br />

Table 45<br />

Types and fuses<br />

Model<br />

Input<br />

current<br />

[Arms]<br />

UL<br />

Class J TD (A)<br />

Mains input fuses<br />

Ferraz-Shawmut<br />

type<br />

SX-D4090-EV 152 175 AJT175<br />

SX-D4110-EV 182 200 AJT200<br />

SX-D4132-EV 216 250 AJT250<br />

SX-*4160-EV 260 300 AJT300<br />

SX-*4200-EV 324 350 AJT350<br />

SX-*4220-EV 372 400 AJT400<br />

SX-*4250-EV 432 500 AJT500<br />

SX-*4315-EV 520 600 AJT600<br />

SX-*4355-EV 562 600 AJT600<br />

SX-*4400-EV 648 700 A4BQ700<br />

SX-*4450-EV 744 800 A4BQ800<br />

SX-*4500-EV 864 1000 A4BQ1000<br />

SX-*4630-EV 1037 1200 A4BQ1200<br />

SX-*4800-EV 1296 1500 A4BQ1500<br />

Omron SX inverter manual Technical Data 177