Energy [733]<br />
Displays the total energy consumption since the last<br />
energy reset [7331] took place.<br />
Unit:<br />
Range:<br />
kWh<br />
0.0–999999kWh<br />
Communication information<br />
Modbus Instance no/DeviceNet no: 31034<br />
Profibus slot/index 121/178<br />
Fieldbus format<br />
Modbus format<br />
Reset Energy [7331]<br />
Resets the kWh counter. The stored information will be<br />
erased and a new registration period will start.<br />
Default:<br />
Selection:<br />
No<br />
No, Yes<br />
Communication information<br />
Modbus Instance no/DeviceNet no: 6<br />
Long, 1=1 W<br />
EInt<br />
Profibus slot/index 0/5<br />
Fieldbus format<br />
Modbus format<br />
733 Energy<br />
Stp<br />
UInt<br />
UInt<br />
kWh<br />
7331 Rst Energy<br />
Stp<br />
No<br />
NOTE: After reset the setting automatically goes back to<br />
“No”.<br />
11.8 View Trip Log [800]<br />
Main menu with parameters for viewing all the logged<br />
trip data. In total the VSD saves the last 10 trips in the<br />
trip memory. The trip memory refreshes on the FIFO<br />
principle (First In, First Out). Every trip in the memory is<br />
logged on the time of the Run Time [731] counter. At<br />
every trip, the actual values of several parameter are<br />
stored and available for troubleshooting.<br />
11.8.1 Trip Message log [810]<br />
Display the cause of the trip and what time that it<br />
occurred. When a trip occurs the status menus are<br />
copied to the trip message log. There are nine trip<br />
message logs [810]–[890]. When the tenth trip occurs<br />
the oldest trip will disappear.<br />
Unit:<br />
Range:<br />
h: m (hours: minutes)<br />
0h: 0m–65355h: 59m<br />
For fieldbus integer value of trip message, see message<br />
table for warnings, [722].<br />
NOTE: Bits 0–5 used for trip message value. Bits 6–15<br />
for internal use.<br />
Communication information<br />
Modbus Instance no/DeviceNet no: 31101<br />
Profibus slot/index 121/245<br />
Fieldbus format<br />
Modbus format<br />
8x0 Trip message<br />
Stp h:mm:ss<br />
810 Ext Trip<br />
Stp 132:12:14<br />
UInt<br />
UInt<br />
Trip message [811]-[81N]<br />
The information from the status menus are copied to<br />
the trip message log when a trip occurs.<br />
Trip menu Copied from Description<br />
811 711 Process Value<br />
812 712 Speed<br />
813 712 Torque<br />
814 714 Shaft Power<br />
815 715 Electrical Power<br />
816 716 Current<br />
817 717 Output voltage<br />
818 718 Frequency<br />
819 719 DC Link voltage<br />
81A 71A Heatsink Temperature<br />
81B 71B PT100_1, 2, 3<br />
81C 721 VSD Status<br />
81D 723 Digital input status<br />
81E 724 Digital output status<br />
81F 725 Analogue input status 1-2<br />
81G 726 Analogue input status 3-4<br />
81H 727 Analogue output status 1-2<br />
146 Functional Description Omron SX inverter manual