Energy [733]<br />

Displays the total energy consumption since the last<br />

energy reset [7331] took place.<br />

Unit:<br />

Range:<br />

kWh<br />

0.0–999999kWh<br />

Communication information<br />

Modbus Instance no/DeviceNet no: 31034<br />

Profibus slot/index 121/178<br />

Fieldbus format<br />

Modbus format<br />

Reset Energy [7331]<br />

Resets the kWh counter. The stored information will be<br />

erased and a new registration period will start.<br />

Default:<br />

Selection:<br />

No<br />

No, Yes<br />

Communication information<br />

Modbus Instance no/DeviceNet no: 6<br />

Long, 1=1 W<br />

EInt<br />

Profibus slot/index 0/5<br />

Fieldbus format<br />

Modbus format<br />

733 Energy<br />

Stp<br />

UInt<br />

UInt<br />

kWh<br />

7331 Rst Energy<br />

Stp<br />

No<br />

NOTE: After reset the setting automatically goes back to<br />

“No”.<br />

11.8 View Trip Log [800]<br />

Main menu with parameters for viewing all the logged<br />

trip data. In total the VSD saves the last 10 trips in the<br />

trip memory. The trip memory refreshes on the FIFO<br />

principle (First In, First Out). Every trip in the memory is<br />

logged on the time of the Run Time [731] counter. At<br />

every trip, the actual values of several parameter are<br />

stored and available for troubleshooting.<br />

11.8.1 Trip Message log [810]<br />

Display the cause of the trip and what time that it<br />

occurred. When a trip occurs the status menus are<br />

copied to the trip message log. There are nine trip<br />

message logs [810]–[890]. When the tenth trip occurs<br />

the oldest trip will disappear.<br />

Unit:<br />

Range:<br />

h: m (hours: minutes)<br />

0h: 0m–65355h: 59m<br />

For fieldbus integer value of trip message, see message<br />

table for warnings, [722].<br />

NOTE: Bits 0–5 used for trip message value. Bits 6–15<br />

for internal use.<br />

Communication information<br />

Modbus Instance no/DeviceNet no: 31101<br />

Profibus slot/index 121/245<br />

Fieldbus format<br />

Modbus format<br />

8x0 Trip message<br />

Stp h:mm:ss<br />

810 Ext Trip<br />

Stp 132:12:14<br />

UInt<br />

UInt<br />

Trip message [811]-[81N]<br />

The information from the status menus are copied to<br />

the trip message log when a trip occurs.<br />

Trip menu Copied from Description<br />

811 711 Process Value<br />

812 712 Speed<br />

813 712 Torque<br />

814 714 Shaft Power<br />

815 715 Electrical Power<br />

816 716 Current<br />

817 717 Output voltage<br />

818 718 Frequency<br />

819 719 DC Link voltage<br />

81A 71A Heatsink Temperature<br />

81B 71B PT100_1, 2, 3<br />

81C 721 VSD Status<br />

81D 723 Digital input status<br />

81E 724 Digital output status<br />

81F 725 Analogue input status 1-2<br />

81G 726 Analogue input status 3-4<br />

81H 727 Analogue output status 1-2<br />

146 Functional Description Omron SX inverter manual