Change Timer [395]<br />
When the time set here is elapsed, the master drive<br />
will be changed. This function is only active if Select<br />
Drive [393]=All and Change Cond [394]= Timer/ Both.<br />
395 Change Timer<br />
StpA<br />
50h<br />
Upper Band [397]<br />
If the speed of the master drive comes into the upper<br />
band, an additional drive will be added after a delay<br />
time that is set in start delay [399].<br />
397 Upper Band<br />
Stp 10%<br />
A<br />
Default:<br />
Range:<br />
50 h<br />
1-3000 h<br />
Default: 10%<br />
Range:<br />
0-100% of total min speed to max speed<br />
Communication information<br />
Modbus Instance no/DeviceNet no: 43165<br />
Profibus slot/index 169/69<br />
Fieldbus format<br />
Modbus format<br />
UInt, 1=1 h<br />
UInt, 1=1 h<br />
Drives on Change [396]<br />
If a master drive is changed according to the timer<br />
function (Change Condition=Timer/Both [394]), it is<br />
possible to leave additional pumps running during the<br />
change operation. With this function the change operation<br />
will be as smooth as possible. The maximum<br />
number to be programmed in this menu depends on<br />
the number of additional drives.<br />
Example:<br />
If the number of drives is set to 6, the maximum value<br />
will be 4. This function is only active if Select Drive<br />
[393]=All.<br />
396 Drives on Ch<br />
Stp A<br />
0<br />
Communication information<br />
Modbus Instance no/DeviceNet no: 43167<br />
Profibus slot/index 169/71<br />
Fieldbus format Long, 1=1%<br />
Modbus format<br />
EInt<br />
Example:<br />
Max Speed = 1500 rpm<br />
Min Speed = 300 rpm<br />
Upper Band = 10%<br />
Start delay will be activated:<br />
Range = Max Speed to Min Speed = 1500–300 =<br />
1200 rpm<br />
10% of 1200 rpm = 120 rpm<br />
Start level = 1500–120 = 1380 rpm<br />
Speed<br />
Max<br />
Upper band<br />
next pump starts<br />
Default: 0<br />
Range: 0 to (the number of drives - 2)<br />
Communication information<br />
Min<br />
Start Delay [399]<br />
Flow/Pressure<br />
(NG_50-PC-12_1)<br />
Modbus Instance no/DeviceNet no: 43166<br />
Fig. 70 Upper band<br />
Profibus slot/index 169/70<br />
Fieldbus format<br />
UInt<br />
Modbus format<br />
UInt<br />
Lower Band [398]<br />
If the speed of the master drive comes into the lower<br />
band an additional drive will be stopped after a delay<br />
time. This delay time is set in the parameter Stop<br />
Delay [39A].<br />
Default: 10%<br />
398 Lower Band<br />
Stp A<br />
10%<br />
104 Functional Description Omron SX inverter manual