Change Timer [395]<br />

When the time set here is elapsed, the master drive<br />

will be changed. This function is only active if Select<br />

Drive [393]=All and Change Cond [394]= Timer/ Both.<br />

395 Change Timer<br />

StpA<br />

50h<br />

Upper Band [397]<br />

If the speed of the master drive comes into the upper<br />

band, an additional drive will be added after a delay<br />

time that is set in start delay [399].<br />

397 Upper Band<br />

Stp 10%<br />

A<br />

Default:<br />

Range:<br />

50 h<br />

1-3000 h<br />

Default: 10%<br />

Range:<br />

0-100% of total min speed to max speed<br />

Communication information<br />

Modbus Instance no/DeviceNet no: 43165<br />

Profibus slot/index 169/69<br />

Fieldbus format<br />

Modbus format<br />

UInt, 1=1 h<br />

UInt, 1=1 h<br />

Drives on Change [396]<br />

If a master drive is changed according to the timer<br />

function (Change Condition=Timer/Both [394]), it is<br />

possible to leave additional pumps running during the<br />

change operation. With this function the change operation<br />

will be as smooth as possible. The maximum<br />

number to be programmed in this menu depends on<br />

the number of additional drives.<br />

Example:<br />

If the number of drives is set to 6, the maximum value<br />

will be 4. This function is only active if Select Drive<br />

[393]=All.<br />

396 Drives on Ch<br />

Stp A<br />

0<br />

Communication information<br />

Modbus Instance no/DeviceNet no: 43167<br />

Profibus slot/index 169/71<br />

Fieldbus format Long, 1=1%<br />

Modbus format<br />

EInt<br />

Example:<br />

Max Speed = 1500 rpm<br />

Min Speed = 300 rpm<br />

Upper Band = 10%<br />

Start delay will be activated:<br />

Range = Max Speed to Min Speed = 1500–300 =<br />

1200 rpm<br />

10% of 1200 rpm = 120 rpm<br />

Start level = 1500–120 = 1380 rpm<br />

Speed<br />

Max<br />

Upper band<br />

next pump starts<br />

Default: 0<br />

Range: 0 to (the number of drives - 2)<br />

Communication information<br />

Min<br />

Start Delay [399]<br />

Flow/Pressure<br />

(NG_50-PC-12_1)<br />

Modbus Instance no/DeviceNet no: 43166<br />

Fig. 70 Upper band<br />

Profibus slot/index 169/70<br />

Fieldbus format<br />

UInt<br />

Modbus format<br />

UInt<br />

Lower Band [398]<br />

If the speed of the master drive comes into the lower<br />

band an additional drive will be stopped after a delay<br />

time. This delay time is set in the parameter Stop<br />

Delay [39A].<br />

Default: 10%<br />

398 Lower Band<br />

Stp A<br />

10%<br />

104 Functional Description Omron SX inverter manual