11.4.2 Process Protection [420]<br />

Submenu with settings regarding protection functions<br />

for the VSD and the motor.<br />

Low Voltage Override [421]<br />

If a dip in the mains supply occurs and the low voltage<br />

override function is enabled, the VSD will automatically<br />

decrease the motor speed to keep control of the<br />

application and prevent an under voltage trip until the<br />

input voltage rises again. Therefore the rotating energy<br />

in the motor/load is used to keep the DC link voltage<br />

level at the override level, for as long as possible or<br />

until the motor comes to a standstill. This is dependent<br />

on the inertia of the motor/load combination and<br />

the load of the motor at the time the dip occurs, see<br />

Fig. 79.<br />

Default: On<br />

Off 0 At a voltage dip the low voltage trip will protect.<br />

On 1<br />

At mains dip, VSD ramps down until voltage<br />

rises.<br />

Communication information<br />

421 Low Volt OR<br />

Stp A<br />

On<br />

Modbus Instance no/DeviceNet no: 43361<br />

Profibus slot/index 170/10<br />

Fieldbus format<br />

UInt<br />

Modbus format<br />

UInt<br />

DC link voltage<br />

Override<br />

level<br />

Low Volt.<br />

level<br />

Rotor locked [422]<br />

With the rotor locked function enabled, the VSD will<br />

protect the motor and application when this is stalled<br />

whilst increasing the motor speed from standstill. This<br />

protection will coast the motor to stop and indicate a<br />

fault when the Torque Limit has been active at very low<br />

speed for more than 5 seconds.<br />

Default: Off<br />

Off 0 No detection<br />

On 1<br />

Communication information<br />

Motor lost [423]<br />

With the motor lost function enabled, the VSD is able<br />

to detect a fault in the motor circuit: motor, motor<br />

cable, thermal relay or output filter. Motor lost will<br />

cause a trip, and the motor will coast to standstill,<br />

when a missing motor phase is detected during a<br />

period of 5 s.<br />

Communication information<br />

VSD will trip when locked rotor is detected.<br />

Trip message “Locked Rotor”.<br />

Modbus Instance no/DeviceNet no: 43362<br />

Profibus slot/index 170/11<br />

Fieldbus format<br />

UInt<br />

Modbus format<br />

UInt<br />

Default:<br />

Off 0<br />

Trip 1<br />

422 Rotor locked<br />

Stp A<br />

Off<br />

423 Motor lost<br />

Stp A<br />

Off<br />

Off<br />

Function switched off to be used if no<br />

motor or very small motor connected.<br />

VSD will trip when the motor is disconnected.<br />

Trip message “Motor Lost”.<br />

Speed<br />

t<br />

Modbus Instance no/DeviceNet no: 43363<br />

Profibus slot/index 170/12<br />

Fieldbus format<br />

UInt<br />

Modbus format<br />

UInt<br />

(06-F60new)<br />

Fig. 79 Low voltage override<br />

t<br />

NOTE: During the low voltage override the LED trip/limit<br />

blinks.<br />

Omron SX inverter manual Functional Description 113