[367] Preset Ref 6, with default 1250 rpm<br />

[368] Preset Ref 7, with default 1500 rpm<br />

The selection of the presets is as in Table 21.<br />

Table 21<br />

Preset<br />

Ctrl3<br />

Preset<br />

Ctrl2<br />

Preset<br />

Ctrl1<br />

Output Speed<br />

Motpot<br />

UP<br />

Motpot<br />

DOWN<br />

Fig. 65 MotPot function<br />

t<br />

t<br />

t<br />

0 0 0 Analogue reference<br />

0 0 1 1) Preset Ref 1<br />

0 1 1) 0 Preset Ref 2<br />

0 1 1 Preset Ref 3<br />

1 1) 0 0 Preset Ref 4<br />

1 0 1 Preset Ref 5<br />

1 1 0 Preset Ref 6<br />

1 1 1 Preset Ref 7<br />

Preset Ref 1 [362] to Preset Ref 7<br />

[368]<br />

Preset speeds have priority over the analogue inputs.<br />

Preset speeds are activated by the digital inputs. The<br />

digital inputs must be set to the function Pres. Ref 1,<br />

Pres. Ref 2 or Pres. Ref 4.<br />

Depending on the number of digital inputs used, up to<br />

7 preset speeds can be activated per parameter set.<br />

Using all the parameter sets, up to 28 preset speeds<br />

are possible.<br />

Default: Speed, 0 rpm<br />

Dependent on: Process Source [321] and Process Unit [322]<br />

Speed mode 0 - max speed [343]<br />

Torque mode 0 - max torque [351]<br />

Other modes<br />

Communication information<br />

362 Preset Ref 1<br />

Stp A 0rpm<br />

Min according to menu [324] - max according<br />

to menu [325]<br />

Modbus Instance no/DeviceNet no: 43132–43138<br />

Profibus slot/index 169/36–169/42<br />

Fieldbus format<br />

Long<br />

Modbus format<br />

EInt<br />

The same settings are valid for the menus:<br />

[363] Preset Ref 2, with default 250 rpm<br />

[364] Preset Ref 3, with default 500 rpm<br />

[365] Preset Ref 4, with default 750 rpm<br />

[366] Preset Ref 5, with default 1000 rpm<br />

1) = selected if only one preset reference is active<br />

1 = active input<br />

0 = non active input<br />

NOTE: If only Preset Ctrl3 is active, then the Preset Ref 4<br />

can be selected. If Presets Ctrl2 and 3 are active, then<br />

the Preset Ref 2, 4 and 6 can be selected.<br />

Keyboard reference mode [369]<br />

This parameter sets how the reference value [310] is<br />

edited.<br />

Default:<br />

Normal 0<br />

MotPot 1<br />

MotPot<br />

Communication information<br />

The reference value is edited as a normal<br />

parameter (the new reference value is<br />

activated when Enter is pressed after the<br />

value has been changed). The Acc Time<br />

[331] and Dec Time [332] are used.<br />

The reference value is edited using the<br />

motor potentiometer function (the new<br />

reference value is activated directly when<br />

the key + or - is pressed). The Acc MotPot<br />

[333] and Dec MotPot [334] are used.<br />

Modbus Instance no/DeviceNet no: 43139<br />

Profibus slot/index 169/43<br />

Fieldbus format<br />

Modbus format<br />

369 Key Ref Mode<br />

StpA<br />

MotPot<br />

UInt<br />

UInt<br />

98 Functional Description Omron SX inverter manual