[367] Preset Ref 6, with default 1250 rpm<br />
[368] Preset Ref 7, with default 1500 rpm<br />
The selection of the presets is as in Table 21.<br />
Table 21<br />
Preset<br />
Ctrl3<br />
Preset<br />
Ctrl2<br />
Preset<br />
Ctrl1<br />
Output Speed<br />
Motpot<br />
UP<br />
Motpot<br />
DOWN<br />
Fig. 65 MotPot function<br />
t<br />
t<br />
t<br />
0 0 0 Analogue reference<br />
0 0 1 1) Preset Ref 1<br />
0 1 1) 0 Preset Ref 2<br />
0 1 1 Preset Ref 3<br />
1 1) 0 0 Preset Ref 4<br />
1 0 1 Preset Ref 5<br />
1 1 0 Preset Ref 6<br />
1 1 1 Preset Ref 7<br />
Preset Ref 1 [362] to Preset Ref 7<br />
[368]<br />
Preset speeds have priority over the analogue inputs.<br />
Preset speeds are activated by the digital inputs. The<br />
digital inputs must be set to the function Pres. Ref 1,<br />
Pres. Ref 2 or Pres. Ref 4.<br />
Depending on the number of digital inputs used, up to<br />
7 preset speeds can be activated per parameter set.<br />
Using all the parameter sets, up to 28 preset speeds<br />
are possible.<br />
Default: Speed, 0 rpm<br />
Dependent on: Process Source [321] and Process Unit [322]<br />
Speed mode 0 - max speed [343]<br />
Torque mode 0 - max torque [351]<br />
Other modes<br />
Communication information<br />
362 Preset Ref 1<br />
Stp A 0rpm<br />
Min according to menu [324] - max according<br />
to menu [325]<br />
Modbus Instance no/DeviceNet no: 43132–43138<br />
Profibus slot/index 169/36–169/42<br />
Fieldbus format<br />
Long<br />
Modbus format<br />
EInt<br />
The same settings are valid for the menus:<br />
[363] Preset Ref 2, with default 250 rpm<br />
[364] Preset Ref 3, with default 500 rpm<br />
[365] Preset Ref 4, with default 750 rpm<br />
[366] Preset Ref 5, with default 1000 rpm<br />
1) = selected if only one preset reference is active<br />
1 = active input<br />
0 = non active input<br />
NOTE: If only Preset Ctrl3 is active, then the Preset Ref 4<br />
can be selected. If Presets Ctrl2 and 3 are active, then<br />
the Preset Ref 2, 4 and 6 can be selected.<br />
Keyboard reference mode [369]<br />
This parameter sets how the reference value [310] is<br />
edited.<br />
Default:<br />
Normal 0<br />
MotPot 1<br />
MotPot<br />
Communication information<br />
The reference value is edited as a normal<br />
parameter (the new reference value is<br />
activated when Enter is pressed after the<br />
value has been changed). The Acc Time<br />
[331] and Dec Time [332] are used.<br />
The reference value is edited using the<br />
motor potentiometer function (the new<br />
reference value is activated directly when<br />
the key + or - is pressed). The Acc MotPot<br />
[333] and Dec MotPot [334] are used.<br />
Modbus Instance no/DeviceNet no: 43139<br />
Profibus slot/index 169/43<br />
Fieldbus format<br />
Modbus format<br />
369 Key Ref Mode<br />
StpA<br />
MotPot<br />
UInt<br />
UInt<br />
98 Functional Description Omron SX inverter manual