11.3.9 Pump/Fan Control [390]<br />

The Pump Control functions are in menu [390]. The<br />

function is used to control a number of drives (pumps,<br />

fans, etc.) of which one is always driven by the VSD.<br />

Pump enable [391]<br />

This function will enable the pump control to set all relevant<br />

pump control functions.<br />

Default: Off<br />

Off 0 Pump control is switched off.<br />

On 1<br />

Communication information<br />

391 Pump enable<br />

Stp A<br />

Off<br />

Pump control is on:<br />

- Pump control parameters [392] to [39G]<br />

appear and are activated according to<br />

default settings.<br />

- View functions [39H] to [39M] are added<br />

in the menu structure.<br />

Modbus Instance no/DeviceNet no: 43161<br />

Profibus slot/index 169/65<br />

Fieldbus format<br />

UInt<br />

Modbus format<br />

UInt<br />

Number of Drives [392]<br />

Sets the total number of drives which are used, including<br />

the Master VSD. The setting here depends on the<br />

parameter Select Drive [393]. After the number of<br />

drives is chosen it is important to set the relays for the<br />

pump control. If the digital inputs are also used for status<br />

feedback, these must be set for the pump control<br />

according to; Pump 1 OK– Pump6 OK in menu [520].<br />

Default: 1<br />

1-3 Number of drives if I/O Board is not used.<br />

1-6<br />

1-7<br />

Communication information<br />

Number of drives if 'Alternating MASTER' is<br />

used, see Select Drive [393]. (I/O Board is<br />

used.)<br />

Number of drives if 'Fixed MASTER' is used,<br />

see Select Drive [393].<br />

(I/O Board is used.)<br />

NOTE: Used relays must be defined as Slave Pump or<br />

Master Pump. Used digital inputs must be defined as<br />

Pump Feedback.<br />

Modbus Instance no/DeviceNet no: 43162<br />

Profibus slot/index 169/66<br />

Fieldbus format<br />

Modbus format<br />

392 No of Drives<br />

Stp A<br />

1<br />

UInt<br />

UInt<br />

Select Drive [393]<br />

Sets the main operation of the pump system.<br />

'Sequence' and 'Runtime' are Fixed MASTER operation.<br />

'All' means Alternating MASTER operation.<br />

393 Select Drive<br />

StpA<br />

Sequence<br />

Default:<br />

Sequence 0<br />

Sequence<br />

Fixed MASTER operation:<br />

- The additional drives will be selected in<br />

sequence, i.e. first pump 1 then pump 2<br />

etc.<br />

- A maximum of 7 drives can be used.<br />

102 Functional Description Omron SX inverter manual