Run Times 1-6 [39H] to [39M]<br />

Unit:<br />

Range:<br />

h:m (hours:minutes)<br />

0h:0m–65535h:59m.<br />

Communication information<br />

Modbus Instance no/<br />

DeviceNet no:<br />

Profibus slot/index<br />

Fieldbus format<br />

Modbus format<br />

Reset Run Times 1-6 [39H1] to [39M1]<br />

Default:<br />

No 0<br />

Yes 1<br />

No<br />

Communication information<br />

Pump Status [39N]<br />

39N Pump 123456<br />

StpA<br />

OCD<br />

31051 hours, 31052 minutes,<br />

31054 hours, 31055 minutes,<br />

31057 hours, 31058 minutes,<br />

31060 hours, 31061 minutes,<br />

31063 hours, 31064 minutes,<br />

31066 hours, 31067 minutes<br />

121/195, 121/198, 121/201,<br />

121/204, 121/207, 121/210<br />

UInt<br />

UInt<br />

Modbus Instance no/DeviceNet no: 38–43, pump 1 -6<br />

Profibus slot/index 0/37–0/42<br />

Fieldbus format<br />

Modbus format<br />

Indication<br />

C<br />

D<br />

O<br />

E<br />

39H Run Time 1<br />

Stp A h:mm<br />

UInt<br />

UInt<br />

Description<br />

Control, master pump, only when alternating<br />

master is used<br />

Direct control<br />

Pump is off<br />

Pump error<br />

39H1 Rst Run Tm1<br />

Stp A<br />

No<br />

11.4 Load Monitor and Process<br />

Protection [400]<br />

11.4.1 Load Monitor [410]<br />

The monitor functions enable the VSD to be used as a<br />

load monitor. Load monitors are used to protect<br />

machines and processes against mechanical overload<br />

and underload, e.g. a conveyer belt or screw conveyer<br />

jamming, belt failure on a fan and a pump dry running.<br />

See explanation in section 7.5, page 40.<br />

Alarm Select [411]<br />

Selects the types of alarms that are active.<br />

Default:<br />

Off<br />

Off 0 No alarm functions active.<br />

Min 1<br />

Max 2<br />

Max+Min 3<br />

Communication information<br />

Alarm Trip [412]<br />

Selects which alarm must cause a trip to the VSD.<br />

Communication information<br />

Min Alarm active. The alarm output functions<br />

as an underload alarm.<br />

Max Alarm active. The alarm output functions<br />

as an overload alarm.<br />

Both Max and Min alarm are active. The<br />

alarm outputs function as overload and<br />

underload alarms.<br />

Modbus Instance no/DeviceNet no: 43321<br />

Profibus slot/index 169/225<br />

Fieldbus format<br />

Modbus format<br />

Default:<br />

Off<br />

Selection: Same as in menu [411]<br />

UInt<br />

UInt<br />

Modbus Instance no/DeviceNet no: 43322<br />

Profibus slot/index 169/226<br />

Fieldbus format<br />

Modbus format<br />

411 Alarm Select<br />

Stp A<br />

Off<br />

412 Alarm trip<br />

Stp A<br />

Off<br />

UInt<br />

UInt<br />

108 Functional Description Omron SX inverter manual