Remote Controllers<br />

5.4 HRV <br />

4, 5<br />

3<br />

6<br />

1, 7<br />

UNIT No.<br />

CODE<br />

GROUP<br />

HR HRV<br />

4 5<br />

3<br />

hr<br />

SETTING<br />

A<br />

hr FRESH UP<br />

2<br />

A<br />

BRC301B61<br />

The following describes the operating procedure and settings.<br />

1 Press the INSPECTION button for more than four seconds to enter<br />

the local setting mode when the unit is in the normal mode.<br />

2 Use the VENTILATION MODE, AIR FLOW RATE button to select<br />

the desired “mode number”. (The code display will blink.)<br />

3 To make setting for individual unit under group control (when mode<br />

no. 27, 28 or 29 is selected), press TIMER SETTING ON / OFF<br />

button to select the “unit No.” for which the settings are to be made.<br />

(This process is not necessary when settings are made collectively<br />

for the group.)<br />

4 Press the top section of the TIMER button to select the “setting<br />

switch No.”.<br />

5 Press the lower section of the TIMER button to select the “setting<br />

position No.”.<br />

6 Press the PROGRAM / CANCEL button once to enter the settings.<br />

(The code display will stop blinking and light up.)<br />

7 Press the INSPECTION button to return to normal mode.<br />

Note:<br />

When you make the plural setting to one (or one group) indoor unit, the item 2 to 6 of the above setting procedure should<br />

be repeated and it should be returned to the “normal mode” by the procedure of item 7 at last.<br />

88 5.4 HRV