Remote Controllers<br />
5.4 HRV <br />
4, 5<br />
3<br />
6<br />
1, 7<br />
UNIT No.<br />
CODE<br />
GROUP<br />
HR HRV<br />
4 5<br />
3<br />
hr<br />
SETTING<br />
A<br />
hr FRESH UP<br />
2<br />
A<br />
BRC301B61<br />
The following describes the operating procedure and settings.<br />
1 Press the INSPECTION button for more than four seconds to enter<br />
the local setting mode when the unit is in the normal mode.<br />
2 Use the VENTILATION MODE, AIR FLOW RATE button to select<br />
the desired “mode number”. (The code display will blink.)<br />
3 To make setting for individual unit under group control (when mode<br />
no. 27, 28 or 29 is selected), press TIMER SETTING ON / OFF<br />
button to select the “unit No.” for which the settings are to be made.<br />
(This process is not necessary when settings are made collectively<br />
for the group.)<br />
4 Press the top section of the TIMER button to select the “setting<br />
switch No.”.<br />
5 Press the lower section of the TIMER button to select the “setting<br />
position No.”.<br />
6 Press the PROGRAM / CANCEL button once to enter the settings.<br />
(The code display will stop blinking and light up.)<br />
7 Press the INSPECTION button to return to normal mode.<br />
Note:<br />
When you make the plural setting to one (or one group) indoor unit, the item 2 to 6 of the above setting procedure should<br />
be repeated and it should be returned to the “normal mode” by the procedure of item 7 at last.<br />
88 5.4 HRV