Outline of D-<strong>BACS</strong> System<br />

Control Method Objective / Use<br />

Building Control<br />

System<br />

Power Proportional<br />

Distribation (P.P.D)<br />

Adaptor<br />

Wiring adaptor for<br />

electrical<br />

appendices (2)<br />

Wiring adaptor for<br />

electrical<br />

appendices (1)<br />

Adaptor for wiring<br />

Adaptor for<br />

connection with<br />

optional<br />

controllers for<br />

centralized control<br />

Building control<br />

computer,<br />

air-conditioning<br />

control computer<br />

and control<br />

system for<br />

air-conditioning<br />

are carried out by<br />

communication<br />

and contact<br />

signal.<br />

Performs<br />

monitoring of<br />

accumulated<br />

charges and<br />

operation for each<br />

indoor unit.<br />

Intelligent Touch<br />

Controller<br />

For control by<br />

operation<br />

command from<br />

BAS<br />

When controlling<br />

operation with<br />

optional<br />

accessories added<br />

inside indoor units,<br />

the status is<br />

displayed outside.<br />

For controlling all<br />

indoor units from<br />

one place<br />

Unit Name and<br />

Model<br />

� Interface for<br />

use in BACnet ®<br />

DMS502B51<br />

� Optional DIII<br />

board<br />

DAM411A1<br />

� Optional Di<br />

Board<br />

DAM412A1<br />

� Parallel<br />

interface<br />

DPF201A51, 52, 53<br />

� Interface for<br />

use in<br />

LONWORKS ®<br />

DMS504B51<br />

� i-Manager III<br />

� intelligent<br />

Touch<br />

Controller<br />

(Proportional<br />

division<br />

software is<br />

used)<br />

� With remote<br />

temperature<br />

setting<br />

KRP4A51<br />

KRP4A52<br />

KRP4A53<br />

KRP4A54<br />

Built into indoor<br />

unit<br />

� With remote<br />

temperature<br />

setting<br />

KRP2A53<br />

KRP2A61<br />

KRP2A62<br />

Built into indoor<br />

unit<br />

Built into indoor unit<br />

KRP1B56, 57, 59, 61<br />

KRP1C3<br />

� Unification<br />

adaptor for<br />

computerized<br />

control<br />

DCS302A52<br />

� Interface<br />

adaptor for<br />

SkyAir series<br />

DTA102A52<br />

� Wiring adaptor<br />

for other air<br />

conditioners<br />

DTA103A51<br />

Function<br />

� Interface for use in BACnet ®<br />

Interface unit to allow communications<br />

between VRV and BMS.<br />

� Parallel interface<br />

Carries out operation and monitoring function<br />

of each indoor unit by contact and analog<br />

signal.<br />

� Interface for use in LONWORKS ®<br />

The LON Gateway functions as the interface for<br />

a building monitoring system and cannot be winstalled<br />

on the DIII-NET along with following<br />

equipment / devices that have similar functions.<br />

� Air conditioning charges are accumulated for<br />

each indoor unit.<br />

� Registration can be made for each tenant.<br />

� Operation/stop/abnormality monitoring for an<br />

indoor unit is available for each tenant.<br />

� Normally open or momentary open type<br />

contactor<br />

� 12~24 VDC or no-voltage<br />

� Various control methods available by mode<br />

select switch<br />

� Voltage, no-voltage selector switch<br />

� Alarm and operation display signal (novoltage)<br />

� Selector switch of zone/individual of alarm<br />

display<br />

� Remote temperature setting (resistance input<br />

of 0~135Ω)<br />

� Selector switch for remote controller<br />

temperature setting enable/inhibit<br />

∗ For group unified control, the setting becomes<br />

the same for all connected indoor units, and<br />

each indoor unit is controlled individually by<br />

built-in thermostat.<br />

∗ In case of using wiring adaptor for Electrical<br />

Appendices (2), the control by 2 remote<br />

controller is not available.<br />

� Function is the same as above.<br />

Used only when 3 groups or more of HRV are<br />

interlocked and operated.<br />

∗ In case of integrated zone control, settings for<br />

all indoor units connected to respective<br />

groups become the same, and each indoor<br />

unit is controlled by built-in thermostats.<br />

� Necessary when electric heater and<br />

humidifier are incorporated optionally<br />

� Operation indicating signal is made by taking<br />

out compressor operation signal.<br />

� Unification adaptor for computerized control<br />

allows you to simultaneously turn indoor units<br />

connected to the central remote controller on<br />

or off or display at the central monitor panel,<br />

etc.<br />

� Interface adaptor for SkyAir series, wiring<br />

adaptor for other air conditioners and wiring<br />

adaptor for ‘H’ indoor unit are for connection of<br />

optional controllers for centralized control.<br />

Note) Central control units such as central remote controller cannot be used at the same time.<br />

Standard Number of<br />

Controllers<br />

Interface for use in<br />

BACnet ® :<br />

Up to 256 indoor<br />

units (256groups)<br />

When the option DIII<br />

board is used<br />

Parallel Interface,<br />

Interface for use in<br />

LONWORKS ®<br />

Up to 64 indoor units<br />

(64 groups)<br />

A charge<br />

management unit<br />

can cover 64 indoor<br />

units.<br />

1 PC board controls<br />

1 indoor unit.<br />

1 PC board<br />

simultaneously<br />

controls 1 group of<br />

indoor units (max. 16<br />

units).<br />

1 adaptor could<br />

control a maximum<br />

of 64 groups with 1<br />

group consisting of a<br />

maximum of 16 units<br />

(up to 126 units in<br />

total).<br />

1 adaptor controls<br />

electric heaters and<br />

humidifiers.<br />

� Simultaneously controls<br />

by one unification adaptor<br />

for computerized control,<br />

all indoor units connected<br />

to a central remote<br />

controller.<br />

� Controls one indoor unit by<br />

one interface adaptor for<br />

SkyAir series, wiring<br />

adaptor for other air<br />

conditioners, and wiring<br />

adaptor for ‘G(J)’ indoor<br />

unit.<br />

12 3.2 Main Specifications and Functions of the Equipment