intelligent Touch Controller<br />

5.3 Wiring for Force Stop Input and for Electric Power Distribution<br />

In order to stop the air-conditioner through force stop input, connect the wiring for force stop input to<br />

the terminals Di1 and COM as shown in the sketch below.<br />

In addition, in order to calculate the electric energy using optional Power Proportional Distribution software,<br />

connect the wiring for electric energy to the terminals Pi and COM as shown in the sketch below.<br />

LAN<br />

Forced OFF contact input<br />

COM Di1 Pi3 COM Pi2 Pi1 F2 F1<br />

N L<br />

~<br />

100-240V<br />

Measuring meter (max 3 units)<br />

(When using an optional Power Proportional Distribution function)<br />

Wiring for force stop input 0.75 - <strong>1.</strong>25mm 2 vinyl cord or cable with sheath (2 wire) -- up to 150m maximum<br />

When FORCE-STOP INPUT is kept ON, the indoor units connected<br />

thereto are unable to be operated because they are force-stopped.<br />

Use a contact which can guarantee minimum application load DC16V and 10mA.<br />

Use an instantaneous contact of 200msec or more in current feed time, where required.<br />

Meter wiring for power<br />

distribution (option)<br />

0.75 - <strong>1.</strong>25mm 2 vinyl cord or cable with sheath (2 wire) -- up to 150m maximum<br />

The number of connectable indoor units is up to 64 units maximum,<br />

where the Power Proportional Distribution Card as option is used.<br />

The measuring meters to be connected must meet the requirements specified below.<br />

To be a measuring meter with pulse oscillator. (pulse/kwh)<br />

Pulse band of 100msec or mores<br />

Measuring meter which uses semiconductor relay for pulse output<br />

and outputs pulses from non-voltage contact<br />

><br />

Don't clamp these cables together with high voltage cables. Failure to observe this instruction would<br />

cause control error.<br />

Terminals COM are inter-connected. Connecting to either one is allowed, but the number of cables<br />

connectable to one terminal is limited to 2 pieces.<br />

Don't connect the power cable to Pi, Di, COM terminal blocks. Wrong connection to these terminal<br />

blocks could result in damage and burning of the centralized control devices and of the electric parts<br />

of the indoor and outdoor units. This is very hazardous. Check each wired cable once more before<br />

turning ON the power switch.<br />