Remote Controllers<br />

4. Various Control by Remote Controller Control<br />

4.1 Group Control<br />

Simultaneous control of up to 16 units with a single remote controller<br />

This is a convenient system for when you want to simultaneously control several indoor units with the same settings for<br />

air conditioning a wide, single floor.<br />

� Wiring for remote controller group control has no polarity, P 1 and P 2 can be switched.<br />

� All indoor units within the group have the same setting, and each indoor unit is controlled individually by its own builtin<br />

thermostat.<br />

� Because automatic address is used, address does not have to be set by remote controller for group control.<br />

Note:<br />

� Only remote controller wiring is shown.<br />

� For Connection unit series<br />

Although group control in Connection unit series is possible, however, group control with other series is impossible.<br />

4.2 Forced OFF or ON/OFF Control<br />

Enables forced OFF or ON/OFF control of indoor unit by input from outside.<br />

Indoor units can be started or stopped by building control or key control system.<br />

Notes<br />

· FXUQ-M(A) : Not available<br />

<strong>1.</strong> Wiring method and specifications<br />

� Remote control can be carried out by connecting input from outside to terminals T 1 and T 2 of the terminal block (for<br />

remote controller transmission wiring).<br />

2. Contents of operation<br />

� Operation is as given in the table on the right for input A of forced OFF and ON/OFF control.<br />

3. How to select forced OFF and ON/OFF control<br />

� Select input by remote controller after turning on the power supply.<br />

� Set to the field set mode by remote controller.<br />

� After entering the field set mode, select mode No. 12, set the first code No. to “1,” and set the second code No. to “01”<br />

for forced OFF, or to “02” for ON/OFF control.<br />

(Factory setting is set to forced OFF.)<br />

Wiring specifications Sheathed vinyl cord or cable (2 wire)<br />

Wiring thickness 0.75~<strong>1.</strong>25 mm²<br />

Wiring length Max. 100 m<br />

Outside contact specifications Contact that guarantees minimum applicable capacity of 15 VDC, 10mA<br />

For forced OFF For ON/OFF control<br />

Forced OFF (remote controller rejection) by input A “ON” Operate by switching input A from “OFF” to “ON”<br />

Remote controller acceptance by input A “OFF” Operate by switching input A from “ON” to “OFF”<br />

76 4.1 Group Control