4. Functions<br />

4.1 Functions<br />

intelligent Touch Controller<br />

Central control device name intelligent Touch Controller<br />

Product name/System name<br />

intelligent Touch Controller main<br />

unit alone<br />

Use with DIII-NET Plus ADP<br />

Model name<br />

Function Details<br />

DCS601C51 DCS601C51+DCS601A52<br />

No. of DIII lines (ports) No. of F1/F2 1 2 (1+1)<br />

Wiring Limitations<br />

Operation setups<br />

No. of controllable indoor<br />

units<br />

No. of controllable zones<br />

No. of outdoor units<br />

Required master-slave<br />

setting when installed in<br />

multiple sites<br />

Control wiring for central<br />

settings<br />

No. of groups 64 128 (64+64)<br />

No. of units connected (Max. No. of<br />

units is 128 per DIII-NET line)<br />

1 zone --- 1 group or more<br />

1 zone --- the same setting for all of<br />

the indoor units.<br />

1 zone is from 1 up to 64 groups<br />

No. of connected units (Max. No. of 10<br />

units per 1 DIII-NET line)<br />

128<br />

(64 when P.P.D. is conducted)<br />

128 128<br />

10 10×2<br />

Connectors, screens and switches On screen: (Master/Slave)<br />

Determine master-slave relationship<br />

for other central control devices<br />

CN1 (Master central setting<br />

connector)<br />

256<br />

(128 when P.P.D. is conducted)<br />

Follows the settings of the<br />

intelligent touch controller unit<br />

CN1 (Master central setting<br />

connector)<br />

Necessity of power supply Yes / Terminal block Yes/N-L Yes/N-L<br />

Operation Touch panel<br />

Method of operation Group Yes<br />

ON (OFF) Group Yes<br />

Unified ON/OFF<br />

Cooling/Heating<br />

changeover<br />

All connected units Yes<br />

By group/zone Yes<br />

By group/zone Yes<br />

Temperature setting By group/zone Yes<br />

Filter sign reset By group/zone Yes<br />

Vane direction change By group/zone Yes<br />

Airflow rate change By group/zone Yes<br />

Ventilation mode By group/zone<br />

Ventilation rate By group/zone<br />

Forced OFF input<br />

Individual remote control<br />

rejection/acceptance<br />

setting<br />

External signal: Non-voltage,<br />

normally open contact, /Main unit<br />

terminal block<br />

0.75-<strong>1.</strong>25 mm 2 up to 150 m<br />

By group/zone<br />

ON/OFF, mode setting and<br />

temperature setting<br />

Operated via the intelligent touch<br />

controller touch panel<br />

Yes<br />

(to be addressed as of the HRV 2005 [G type] model)<br />

Yes<br />

(to be addressed as of the HRV 2006 [GA type] model)<br />

4.1 Functions 101<br />

Yes<br />

Yes<br />

Yes<br />

(Forced OFF (shutdown) is input<br />

from the contact point of the<br />

intelligent touch controller main<br />

body and conducted<br />

simultaneously with shutdown<br />

(forced OFF) of the A/C units<br />

connected to the intelligent touch<br />

controller unit.)