5.9.3 PPD (Power Proportional Distribution) Application (DCS002C51)<br />
The power consumption<br />
of the outdoor unit can<br />
be proportionally<br />
calculated for each<br />
indoor unit using the<br />
intelligent touch<br />
controller and the<br />
Power Proportional<br />
Distribution software.<br />
The calculated results<br />
are recorded in the<br />
intelligent touch<br />
controller for 13 months.<br />
The calculated results<br />
can be taken out with<br />
the PCMCIA card so<br />
that the data can be<br />
handled using any<br />
spreadsheet software<br />
including Excel on the<br />
PC.<br />
Note)<br />
Equipment<br />
Option for Intelligent<br />
Touch Controller (P.P.D)<br />
kW·h meter<br />
Power<br />
Supply<br />
3φ 4W 380-415V<br />
50Hz<br />
Refer to field wiring on previous<br />
page about power supply wiring.<br />
Intelligent Touch<br />
Controller<br />
Arrangement<br />
DAIKIN<br />
DAIKIN<br />
Field Supply<br />
kWh-meters<br />
[Field Supply]<br />
Model/Spec<br />
DCS601C51<br />
DCS002C51<br />
Pulse<br />
transmitter<br />
DCS601C51 (Back side)<br />
Remark<br />
DIII-NET<br />
Up to 64 groups can be connected<br />
Activation number card included<br />
PCMCIA card included<br />
•1 pulse to 1kW·h or 10kW·h pulse width must be<br />
within 40-400m/sec.<br />
Output relay must be or electronic type only.<br />
No voltage output.<br />
CSV output of PPD PCMCIA<br />
[DAIKIN option attached PPD]<br />
intelligent Touch Controller<br />
5.9 Wiring Example for intelligent Touch Controller (DCS601C51) 113<br />
Switch<br />
L1 L2 L3 N<br />
Outdoor Unit<br />
DAIKIN<br />
The optional Power Proportional<br />
Distribution (PPD) results can be saved<br />
to a CSV file.<br />
A B C F1F2F1F2 Q1Q2<br />
L1 L2 L3 N<br />
Outdoor Unit<br />
A B C F1F2F1F2 Q1Q2<br />
L1 L2 L3 N<br />
Outdoor Unit<br />
A B C F1F2F1F2 Q1Q2<br />
Power Supply<br />
1φ 220-240V 50Hz<br />
L1 L2<br />
up to 64 units of<br />
A/Cs and equipment<br />
Outdoor Unit<br />
Indoor Unit<br />
F1 F2 P1 P2<br />
Indoor Unit<br />
F1 F2 P1 P2<br />
L3 N<br />
R/C<br />
A B C F1 F2 F1 F2 Q1 Q2<br />
R/C<br />
L1 L2 L3 N<br />
Outdoor Unit<br />
A B C F1 F2 F1 F2 Q1 Q2<br />
R/C<br />
Indoor Unit<br />
F1 F2 P1 P2<br />
R/C<br />
Power Supply<br />
DIII<br />
Contact Signal<br />
Remote Control