26.12.2012 Views

1. D-BACS - Daikin

1. D-BACS - Daikin

1. D-BACS - Daikin

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

5.9.3 PPD (Power Proportional Distribution) Application (DCS002C51)<br />

The power consumption<br />

of the outdoor unit can<br />

be proportionally<br />

calculated for each<br />

indoor unit using the<br />

intelligent touch<br />

controller and the<br />

Power Proportional<br />

Distribution software.<br />

The calculated results<br />

are recorded in the<br />

intelligent touch<br />

controller for 13 months.<br />

The calculated results<br />

can be taken out with<br />

the PCMCIA card so<br />

that the data can be<br />

handled using any<br />

spreadsheet software<br />

including Excel on the<br />

PC.<br />

Note)<br />

Equipment<br />

Option for Intelligent<br />

Touch Controller (P.P.D)<br />

kW·h meter<br />

Power<br />

Supply<br />

3φ 4W 380-415V<br />

50Hz<br />

Refer to field wiring on previous<br />

page about power supply wiring.<br />

Intelligent Touch<br />

Controller<br />

Arrangement<br />

DAIKIN<br />

DAIKIN<br />

Field Supply<br />

kWh-meters<br />

[Field Supply]<br />

Model/Spec<br />

DCS601C51<br />

DCS002C51<br />

Pulse<br />

transmitter<br />

DCS601C51 (Back side)<br />

Remark<br />

DIII-NET<br />

Up to 64 groups can be connected<br />

Activation number card included<br />

PCMCIA card included<br />

•1 pulse to 1kW·h or 10kW·h pulse width must be<br />

within 40-400m/sec.<br />

Output relay must be or electronic type only.<br />

No voltage output.<br />

CSV output of PPD PCMCIA<br />

[DAIKIN option attached PPD]<br />

intelligent Touch Controller<br />

5.9 Wiring Example for intelligent Touch Controller (DCS601C51) 113<br />

Switch<br />

L1 L2 L3 N<br />

Outdoor Unit<br />

DAIKIN<br />

The optional Power Proportional<br />

Distribution (PPD) results can be saved<br />

to a CSV file.<br />

A B C F1F2F1F2 Q1Q2<br />

L1 L2 L3 N<br />

Outdoor Unit<br />

A B C F1F2F1F2 Q1Q2<br />

L1 L2 L3 N<br />

Outdoor Unit<br />

A B C F1F2F1F2 Q1Q2<br />

Power Supply<br />

1φ 220-240V 50Hz<br />

L1 L2<br />

up to 64 units of<br />

A/Cs and equipment<br />

Outdoor Unit<br />

Indoor Unit<br />

F1 F2 P1 P2<br />

Indoor Unit<br />

F1 F2 P1 P2<br />

L3 N<br />

R/C<br />

A B C F1 F2 F1 F2 Q1 Q2<br />

R/C<br />

L1 L2 L3 N<br />

Outdoor Unit<br />

A B C F1 F2 F1 F2 Q1 Q2<br />

R/C<br />

Indoor Unit<br />

F1 F2 P1 P2<br />

R/C<br />

Power Supply<br />

DIII<br />

Contact Signal<br />

Remote Control

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!