6.4.4 HRV Wired Remote Controller <br />

Fundamental of DIII-NET<br />

The following shows the procedure how to set the group number for the centralized controller by the remote controller for indoor unit.<br />

<br />

Purpose<br />

Controller<br />

When you use the central � Remote controller for indoor unit BRC1C62<br />

remote controller and the<br />

unified ON / OFF controller, you<br />

have to set the each unit<br />

connected to the central<br />

transmission line.<br />

Central remote controller<br />

or<br />

ON / OFF controller<br />

[1-00] [1-01]<br />

[1-02]<br />

No necessary<br />

[1-03]<br />

Remote controller<br />

for indoor unit<br />

� BRC301B61<br />

UNIT No.<br />

CODE<br />

GROUP<br />

HRV<br />

Note:<br />

Do not duplicate the group number.<br />

Be sure to supply the power to the remote controller side.<br />

(It cannot be set without the power supply.)<br />

4<br />

5<br />

3<br />

6<br />

1 7<br />

4 5<br />

3<br />

hr<br />

SETTING<br />

A<br />

hr FRESH UP<br />

Operating procedure<br />

The unit in [ ] does not require the group no.<br />

setting for the centralized controller<br />

connected to the central transmission line.<br />

(Auto-address setting)<br />

1 Press the INSPECTION button for more than<br />

four seconds.<br />

2 Use the VENTILATION MODE, AIR FLOW<br />

RATE to select the mode no. “00”.<br />

3 Use the top or lower section of the TIMER<br />

button to set the group no. for the centralized<br />

controller.<br />

(When you use the unified ON / OFF<br />

controller, it displays only the group no.<br />

selected by the setting switch for zone<br />

control.)<br />

4 Press the PROGRAM / CANCEL button to<br />

enter the setting group no. shown on the<br />

display.<br />

5 Press INSPECTION button to return to normal<br />

mode.<br />

6.4 Setting Group No. for Centralized Control 45<br />

2<br />

A<br />

BRC301B61