26.12.2012 Views

1. D-BACS - Daikin

1. D-BACS - Daikin

1. D-BACS - Daikin

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

intelligent Touch Controller<br />

Title Description Remarks<br />

Timing of E-mail<br />

message<br />

transmission<br />

Timing of setting E-mail message<br />

The following figure presents an example of timing the setting of an E-mail message.<br />

[Sending message when an abnormality has occurred under normal conditions]<br />

If an abnormality occurs in a target group of mail messages being sent, the system<br />

waits for 3 minutes since the first abnormality ((1) in the figure) before sending a<br />

mail message.<br />

* A mail message is not sent immediately after the occurrence of an abnormality.<br />

If any abnormality occurs in other groups ((2) and (3) in the figure) during the 3-minute<br />

waiting period, the abnormalities are notified collectively via a single E-mail message.<br />

[Resending a mail message]<br />

As shown in group B, if an abnormality continues after a time interval has elapsed<br />

since transmission of the first mail message, a mail message is resent.<br />

In addition, if a group recovers from an abnormality after sending a mail message and<br />

another abnormality recurs in the same group ((5) in the figure), the latest abnormality<br />

is sent in the message after the sending interval has elapsed.<br />

If another abnormality occurs within the time interval of sending messages ((4) in the<br />

figure), the abnormality is sent in the message after the sending interval has elapsed.<br />

If no abnormality is detected after the sending interval has elapsed, the system stops<br />

sending messages and reverts back to normal.<br />

*: The symbol in the figure indicates the occurrence of an abnormality,<br />

while the symbol in the figure indicates recovery from the same.<br />

Normal<br />

condition<br />

Group A<br />

Group B<br />

Group C<br />

Group D<br />

Re-sending conditions<br />

3 minutes since<br />

the occurrence of<br />

an abnormality<br />

Sending interval<br />

�<br />

�<br />

�<br />

Send abnormality<br />

of groups A, B,<br />

and C<br />

�<br />

�<br />

Timing of E-mail transmission<br />

Sending interval<br />

Send abnormality of<br />

groups B, C, and D<br />

Group B: Abnormality<br />

continues<br />

Group C: Abnormality<br />

recurred<br />

Group D: Another<br />

abnormality<br />

occurred<br />

Normal<br />

condition<br />

If no abnormality is<br />

detected, the<br />

system stops<br />

sending messages<br />

and reverts to<br />

normal conditions<br />

to monitor the air<br />

conditioner.<br />