Fundamental of DIII-NET<br />

5.3 Number of Units to be Connected [VRV] (Supplementary Explanation)<br />

Up to 10 VRV outdoor units can be connected to DIII-NET.<br />

- An outdoor unit which consists of multiple modules is counted as one unit.<br />

Up to 64 VRV indoor units can be connected to DIII-NET.<br />

- If you create remote control groups of indoor units, up to 128 units can be connected. (Max. number of groups is<br />

64.)<br />

- When you use proportional power, the number of indoor units that can be connected is 64 units at the maximum<br />

even if you create remote control groups.<br />

[Example]<br />

In the case of 64 units in total<br />

2-unit module 3-unit module<br />

Each module is<br />

counted as 1 unit.<br />

All the units can be connected by integrating them into 64<br />

groups using remote control groups.<br />

38 5.3 Number of Units to be Connected [VRV] (Supplementary Explanation)