1.3. Električna izvedba<br />
1.3.1. Napon i frekvencija<br />
Prema <strong>EN</strong> 60<strong>03</strong>4-1 rasipanje standardnih<br />
napona i frekvencija mogu biti u kategoiji<br />
A (kombinacija odstupanja napona +- 5% i<br />
odstupanja frekvencije +-2%) i kategoriji B<br />
(kombinacija odstupanja napona +-10% i<br />
devijacije frekvencije +3 -5%). Naši motori mogu<br />
dati nazivni moment u obje kategorije (A i B). U<br />
kategoriji A, zagrijavanje je oko 10K veće nego<br />
tijekom nazivnog pogona. Prema standardu,<br />
duži pogon nije preporučen za kategoriju B.<br />
Norma IEC 60<strong>03</strong>8 standardi propisuju toleranciju<br />
+-10% za glavne napone 230V, 400V i 690V.<br />
Trofazni kavezni asinkroni motori nazivnih<br />
snaga do 2.2kW izrađuju se standardno za<br />
napon 230/400V (spoj D/Y), a motori nazivnih<br />
snaga iznad 3kW za napon 400/690V (spoj D/Y).<br />
Nazivna frekvencija je 50Hz.<br />
Elektromotori izrađeni za frekvenciju izvora<br />
napajanja 50Hz mogu se priključiti na izvor<br />
napajanja frekvencije 60Hz, pri čemu će<br />
brzina vrtnje motora porasti približno 20%.<br />
Izlazne karakteristike su date u tablici tehničkih<br />
podataka za 50Hz i 60Hz.<br />
Ukoliko se uz povećanje frekvencije u istom<br />
omjeru povećao i napon izvora napajanja,<br />
motor se smije opteretiti s približno 15% većom<br />
snagom od snaga koje su navedene u tablici<br />
Tehnički podaci. Iznosi Ik/In, Mk/Mn i Mmax/Mn<br />
ostaju približno isti.<br />
Ukoliko je uz povećanje frekvencije napon<br />
izvora napajanja ostao isti, tada se snaga motora<br />
ne smije povećavati, a iznosi Ik/In, Mk/Mn i Mm/<br />
Mn smanjuju se na vrijednosti približno 85%<br />
od vrijednosti navedenih u tablici Tehničkih<br />
podataka.<br />
Elektromotori namijenjeni za druge napone i<br />
frekvenciju izrađuju se na poseban upit.<br />
1.3. Electrical features<br />
1.3.1.Voltage and frequency<br />
Acc. to <strong>EN</strong> 60<strong>03</strong>4-1 standard voltages and frequency<br />
fluctuations can be in Category A (combination of<br />
voltage deviation ±5 % and frequency deviation<br />
±2 %) and Category B (combination of voltage<br />
deviation ±10 % and frequency deviation +3/–5<br />
%). Our motors can supply their rated torque in<br />
both Category A and Category B. In Category A, the<br />
temperature rise is approx. 10 K higher than during<br />
rated duty. According to the standard, longer duty<br />
is not recommended for Category B. Standard IEC<br />
60<strong>03</strong>8 standard specifies a tolerance of ±10 % for<br />
mains voltages of 230 V, 400 V and 690 V.<br />
Three-phase squirrel cage induction motors with<br />
rated power up to 2,2 kW are made, as standard,<br />
for voltage 230/400V (connection D/Y), and<br />
motors with rated power 3 kW and above for<br />
voltage 400/690V (connection D/Y). Nominal<br />
frequency is 50Hz.<br />
Electric motors produced for power source<br />
frequency of 50 Hz can be connected to the power<br />
source with frequency of 60 Hz, whereas motor<br />
revolving speed will be increased by approximately<br />
20%. The outputs or rated characteristic are given<br />
in Technical Data tables for both 50 Hz and 60 Hz.<br />
If voltage of power source is simultaneously<br />
increased with frequency increase in the same<br />
ratio, motor can be loaded with approximately<br />
15% higher power than powers given in table<br />
Technical data. Values Ik/In, Mk/Mn and Mmax/<br />
Mn remain the same.<br />
If frequency is increased and voltage of power<br />
source remains the same, than motor power must<br />
not be increased and values Ik/In, Mk/Mn i Mm/<br />
Mn are reduced to 85% of values given in the table<br />
Technical data.<br />
Electric motors intended to be used for other<br />
combinations of voltage and frequency – on<br />
request.<br />
ELEKTROMOTORI<br />
1.3. Elektrische Ausführung<br />
1.3.1.Spannung und Frequenz<br />
In Bezug auf <strong>EN</strong> 60<strong>03</strong>4-1 kann die Verstreuung<br />
der standarmäsigen Spannungen und<br />
Frequenzen in der Kategorie A (die<br />
Kombination der Spannungsabweichung<br />
± 5 % und der Frequenzabweichung ± 2<br />
%) und in der Kategorie B (die Kombination<br />
der Spannungsabweichung ± 10 % und der<br />
Frequenzabweichung ± 3/-5 %) sein werden.<br />
Unsere Motoren können das Nennmoment in<br />
beiden Kategorien (A und B) abgeben. In der<br />
Kategorie A, ist die Erwärmung um etwa 10K<br />
höher als im Nennbetrieb. Nach der Norm ist<br />
ein längerer Betrieb nicht für die Kategorie B<br />
zu empfehlen. Die Norm IEC 60<strong>03</strong>8 schreibt die<br />
Toleranz ±10 % für Netzspannungen 230 V, 400<br />
V und 690 V vor.<br />
Dreiphasige Asynchronmotoren mit Käfigläufer<br />
der Nennleistungen bis 2.2kW sind serienmäßig<br />
für die Spannung 230/400V (Schaltung D/Y)<br />
und die Motoren der Nennleistungen über 3kW<br />
für die Spannung 400/690V (Schaltung D/Y)<br />
gefertigt.<br />
Die Nennfrequenz beträgt 50Hz.<br />
Die Elektromotoren gefertigt für die Frequenz<br />
der Speiseqülle von 50Hz kann man auf die<br />
Speiseqülle der Frequenz von 60Hz anschließen<br />
wobei die Drehgeschwindigkeit des Motors um<br />
etwa 20% steigen wird.<br />
Die Ausgangscharakteristiken sind in der Tabelle<br />
der technischen Daten für 50 Hz und 60 Hz<br />
gegeben.<br />
Wenn sich bei der Frequenzerhöhung im<br />
gleichen Verhältnis auch die Spannungsquelle<br />
erhöht hat, kann man den Motor mit annähernd<br />
15% höheren Leistung von den in der Tabelle<br />
technischer Daten gegebenen Werten belasten.<br />
Die Werte Ik/In, Mk/Mn und Mmax/Mn bleiben<br />
dabei annähernd unverändert.<br />
Wenn bei der Frequenzerhöhung die Spannung<br />
der Speiseqülle gleichgeblieben ist, darf man<br />
die Motorleistung nicht erhöhen und die Werte<br />
Ik/In, Mk/Mn und Mm/Mn verringern sich<br />
annähernd auf 85% der Werte, die in der Tabelle<br />
technischer Daten gegeben sind.<br />
Die Elektromotoren für andere Spannungen<br />
und Frequenz fertigt man auf Sonderanfrage.<br />