1.3.6. Električna zaštita<br />
Motori u pogonu trebaju biti zaštićeni od<br />
kratkog spoja, preopterećenja i pregrijavanja.<br />
Kao sredstva zaštite mogu poslužiti osigurači,<br />
sklopnici s bimetalnim okidačima i motorne<br />
zaštitne sklopke.<br />
• Osigurači s tromim ili brzim okidanjem<br />
nedovoljna su zaštita motora. Oni štite<br />
motor samo od kratkog spoja, ali ne<br />
i od preopterećenja ili pregrijavanja.<br />
Rastavne uloške osigurača u dovodnom<br />
krugu motora treba odabrati prema struji<br />
pokretanja. Za izravno uklapanje motora<br />
čije vrijeme zaleta iznosi do 5 sekundi<br />
dovoljni su tromi ulošci osigurača čija struja<br />
odgovara 1.3 x In motora. Za motore koji<br />
se uklapaju preklopkama zvijezda – trokut<br />
dovoljni su tromi ulošci čija struja odgovara<br />
nazivnoj struji motora.<br />
• Sklopnici s bimetalnim okidačima štite<br />
motor od oštećenja koja nastaju uslijed<br />
preopterećenja. Kod motora koji rade u<br />
trajnom pogonu S1 bimetalni okidači<br />
podešavaju se na vrijednost nazivne<br />
struje motora. U tom slučaju oni štite<br />
motor od pregrijavanja koje nastaje zbog<br />
preopterećenja radnog stroja, smanjenjem<br />
ili povećanjem napona izvora napajanja<br />
ili gubitka jedne faze. Ovisno o duljini<br />
trajanja zaleta bimetalni okidači omogućuju<br />
nesmetani zalet motora. Za zaštitu od<br />
kratkog spoja potrebno je ispred sklopnika<br />
dodati trome osigurače.<br />
• Motorna zaštitna sklopka je uređaj koji<br />
omogućuje ukapčanje i iskapčanje motora,<br />
a istovremeno zaštićuje motor. U sklopku<br />
su ugrađeni bimetalni okidači za zaštitu<br />
od preopterećenja i brzi elektromagnetski<br />
okidači za zaštitu od kratkog spoja. Takve<br />
sklopke se mogu opremiti i podnaponskim<br />
okidačem koji isključuje motor s napajanja<br />
ukoliko napon padne na 50% vrijednosti ili<br />
nestane napona napajanja. Podnaponski<br />
okidač ujedno isključuje i samu sklopku.<br />
Nakon što je nestao uzrok isklapanja<br />
sklopke, sklopku treba ponovo ukopčati<br />
ručno, pritiskom na tipkalo.<br />
1.3.6. Electrical protection<br />
Motor during operation must be protected from<br />
short circuit, overloads and overheating. The<br />
following may be used as protection instruments:<br />
fuses, contactors with bimetal triggers and motor<br />
protection circuit breaker.<br />
• Fuses with inert or fast triggering are not<br />
sufficient as motor protection. They protect<br />
motor only from short circuit but not from<br />
overload or overheating. Melting cartridges<br />
of fuses in supplying circuit should be<br />
selected according to starting current. For<br />
direct switching of motors with starting<br />
time up to 5 sec., fuses with inert cartridges<br />
are sufficient, where current is equal 1.3 x In<br />
of motor. For motors which are switched<br />
through star-delta switches inert fuses using<br />
the same current as motor rated current.<br />
• Contactors with bimetal triggers protect<br />
motor from damages due to overload. In<br />
continuously operating motors (S1 duty)<br />
bimetal triggers are calibrated to the value of<br />
motor rated current. In this case they protect<br />
motor from overheating occuring because<br />
of driving machine overload, reduced or<br />
increased power supply voltage or loss of one<br />
phase. Depending on starting time, bimetal<br />
trigger enabling unobstructed motor starts.<br />
For short circuit protection it is necessary to<br />
connect inert fuses in the front of contactor.<br />
• Motor protection circuit breaker is device<br />
which enables motor switching on and<br />
off and at the same time protects motor.<br />
Bimetal triggers are installed in circuit<br />
breakers as overload protection and fast<br />
electromagnetic triggers as short circuit<br />
protection. Such circuit breakers can be<br />
equipped with undervoltage trigger for<br />
power supply disconnection if voltage drops<br />
to 50% of value or because of total lack of<br />
power supply. Undervoltage trigger switches<br />
off the switch itself at the same time. After<br />
the cause of switching off has been removed,<br />
the switch must be switched on manually by<br />
pressing the button.<br />
1.3.6. Elektrischer Schutz<br />
ELEKTROMOTORI<br />
Die Motoren sollen im Betrieb gegen den<br />
Kurzschluss, Überlastung und Überhitzung<br />
geschützt sein. Als Schutzmittel dienen<br />
Sicherungen, Schützen mit Bimetallauslöser und<br />
Motorschutzschalter.<br />
• Schmelzsicherungen mit trägen oder<br />
schnellen Auslösern sind für den<br />
Motorschutz nicht ausreichend. Sie schützen<br />
den Motor nur gegen Kurzschluss aber nicht<br />
gegen Überlastung oder Überhitzung. Die<br />
Schmelzeinsätze der Sicherungen in dem<br />
Zuleitungskreis des Motors soll man nach<br />
dem Anlaufstrom auswählen. Für direktes<br />
Einschalten des Motors, dessen Anlaufzeit<br />
bis zu 5 Sekunden beträgt, genügen die<br />
träge Schmelzeinsätze der Sicherungen,<br />
deren Strom 1.3 x In des Motors entspricht.<br />
Für die Motoren, die mit dem Stern-Dreieck<br />
Umschalter eingeschaltet werden, genügen<br />
die träge Schmelzeinsätze, deren Strom dem<br />
Nennstrom des Motors entspricht.<br />
• Schalter mit Bimetallauslösern schützen den<br />
Motor vor Beschädigungen die infolge einer<br />
Überlastung entstehen können. Bei Motoren<br />
im Daürbetrieb S1 werden die Auslöser auf<br />
den Nennstrom des Motors eingestellt.<br />
Dann schützen sie den Motor gegen<br />
Überhitzung, die durch Überbelastung der<br />
Arbeitsmaschine, Nennspannungsabfall,<br />
bzw. Erhöhung oder Unterbrechung in<br />
einer Phase der Zuleitung entstehen kann.<br />
Abhängig vom Anlaufdauer ermöglichen<br />
die Schalter mit Bimetallauslösern einen<br />
einwandfreien Anlauf des Motors. Als<br />
Schutz vor dem Kurzschluss muss man in<br />
die Zuleitungen vor den Schaltern träge<br />
Sicherungen einsetzen.<br />
• Motorschutzschalter ist eine Einrichtung,<br />
die dazu dient, den Motor ein- und<br />
ausschalten und ihn gleichzeitig zu<br />
schützen. In dem Schalter sind Bimetallrelais<br />
für den Schutz gegen Überlastung und<br />
elektromagnetische Schnellauslöser zum<br />
Schutz gegen Kurzschluss eingebaut.<br />
Die Motorschutzschalter können auch<br />
mit einem Unterspannungsauslöser<br />
ausgerüstet werden, welcher im Falle<br />
des Netzspannungsabfalls auf 50% des<br />
Nennspannungswertes oder völligen<br />
Spannungsausfalls den Motor vom Netz<br />
abtrennt. Der Unterspannungsauslöser<br />
schaltet gleichzeitig auch den<br />
Motorschutzschalter aus. Nach dem<br />
Verschwinden der Ursache für das<br />
Ausschalten des Schalters, muss man<br />
ihn wieder per Handdruck auf den Taster<br />
einschalten.<br />
37