1.3.6. Električna zaštita<br />

Motori u pogonu trebaju biti zaštićeni od<br />

kratkog spoja, preopterećenja i pregrijavanja.<br />

Kao sredstva zaštite mogu poslužiti osigurači,<br />

sklopnici s bimetalnim okidačima i motorne<br />

zaštitne sklopke.<br />

• Osigurači s tromim ili brzim okidanjem<br />

nedovoljna su zaštita motora. Oni štite<br />

motor samo od kratkog spoja, ali ne<br />

i od preopterećenja ili pregrijavanja.<br />

Rastavne uloške osigurača u dovodnom<br />

krugu motora treba odabrati prema struji<br />

pokretanja. Za izravno uklapanje motora<br />

čije vrijeme zaleta iznosi do 5 sekundi<br />

dovoljni su tromi ulošci osigurača čija struja<br />

odgovara 1.3 x In motora. Za motore koji<br />

se uklapaju preklopkama zvijezda – trokut<br />

dovoljni su tromi ulošci čija struja odgovara<br />

nazivnoj struji motora.<br />

• Sklopnici s bimetalnim okidačima štite<br />

motor od oštećenja koja nastaju uslijed<br />

preopterećenja. Kod motora koji rade u<br />

trajnom pogonu S1 bimetalni okidači<br />

podešavaju se na vrijednost nazivne<br />

struje motora. U tom slučaju oni štite<br />

motor od pregrijavanja koje nastaje zbog<br />

preopterećenja radnog stroja, smanjenjem<br />

ili povećanjem napona izvora napajanja<br />

ili gubitka jedne faze. Ovisno o duljini<br />

trajanja zaleta bimetalni okidači omogućuju<br />

nesmetani zalet motora. Za zaštitu od<br />

kratkog spoja potrebno je ispred sklopnika<br />

dodati trome osigurače.<br />

• Motorna zaštitna sklopka je uređaj koji<br />

omogućuje ukapčanje i iskapčanje motora,<br />

a istovremeno zaštićuje motor. U sklopku<br />

su ugrađeni bimetalni okidači za zaštitu<br />

od preopterećenja i brzi elektromagnetski<br />

okidači za zaštitu od kratkog spoja. Takve<br />

sklopke se mogu opremiti i podnaponskim<br />

okidačem koji isključuje motor s napajanja<br />

ukoliko napon padne na 50% vrijednosti ili<br />

nestane napona napajanja. Podnaponski<br />

okidač ujedno isključuje i samu sklopku.<br />

Nakon što je nestao uzrok isklapanja<br />

sklopke, sklopku treba ponovo ukopčati<br />

ručno, pritiskom na tipkalo.<br />

1.3.6. Electrical protection<br />

Motor during operation must be protected from<br />

short circuit, overloads and overheating. The<br />

following may be used as protection instruments:<br />

fuses, contactors with bimetal triggers and motor<br />

protection circuit breaker.<br />

• Fuses with inert or fast triggering are not<br />

sufficient as motor protection. They protect<br />

motor only from short circuit but not from<br />

overload or overheating. Melting cartridges<br />

of fuses in supplying circuit should be<br />

selected according to starting current. For<br />

direct switching of motors with starting<br />

time up to 5 sec., fuses with inert cartridges<br />

are sufficient, where current is equal 1.3 x In<br />

of motor. For motors which are switched<br />

through star-delta switches inert fuses using<br />

the same current as motor rated current.<br />

• Contactors with bimetal triggers protect<br />

motor from damages due to overload. In<br />

continuously operating motors (S1 duty)<br />

bimetal triggers are calibrated to the value of<br />

motor rated current. In this case they protect<br />

motor from overheating occuring because<br />

of driving machine overload, reduced or<br />

increased power supply voltage or loss of one<br />

phase. Depending on starting time, bimetal<br />

trigger enabling unobstructed motor starts.<br />

For short circuit protection it is necessary to<br />

connect inert fuses in the front of contactor.<br />

• Motor protection circuit breaker is device<br />

which enables motor switching on and<br />

off and at the same time protects motor.<br />

Bimetal triggers are installed in circuit<br />

breakers as overload protection and fast<br />

electromagnetic triggers as short circuit<br />

protection. Such circuit breakers can be<br />

equipped with undervoltage trigger for<br />

power supply disconnection if voltage drops<br />

to 50% of value or because of total lack of<br />

power supply. Undervoltage trigger switches<br />

off the switch itself at the same time. After<br />

the cause of switching off has been removed,<br />

the switch must be switched on manually by<br />

pressing the button.<br />

1.3.6. Elektrischer Schutz<br />

ELEKTROMOTORI<br />

Die Motoren sollen im Betrieb gegen den<br />

Kurzschluss, Überlastung und Überhitzung<br />

geschützt sein. Als Schutzmittel dienen<br />

Sicherungen, Schützen mit Bimetallauslöser und<br />

Motorschutzschalter.<br />

• Schmelzsicherungen mit trägen oder<br />

schnellen Auslösern sind für den<br />

Motorschutz nicht ausreichend. Sie schützen<br />

den Motor nur gegen Kurzschluss aber nicht<br />

gegen Überlastung oder Überhitzung. Die<br />

Schmelzeinsätze der Sicherungen in dem<br />

Zuleitungskreis des Motors soll man nach<br />

dem Anlaufstrom auswählen. Für direktes<br />

Einschalten des Motors, dessen Anlaufzeit<br />

bis zu 5 Sekunden beträgt, genügen die<br />

träge Schmelzeinsätze der Sicherungen,<br />

deren Strom 1.3 x In des Motors entspricht.<br />

Für die Motoren, die mit dem Stern-Dreieck<br />

Umschalter eingeschaltet werden, genügen<br />

die träge Schmelzeinsätze, deren Strom dem<br />

Nennstrom des Motors entspricht.<br />

• Schalter mit Bimetallauslösern schützen den<br />

Motor vor Beschädigungen die infolge einer<br />

Überlastung entstehen können. Bei Motoren<br />

im Daürbetrieb S1 werden die Auslöser auf<br />

den Nennstrom des Motors eingestellt.<br />

Dann schützen sie den Motor gegen<br />

Überhitzung, die durch Überbelastung der<br />

Arbeitsmaschine, Nennspannungsabfall,<br />

bzw. Erhöhung oder Unterbrechung in<br />

einer Phase der Zuleitung entstehen kann.<br />

Abhängig vom Anlaufdauer ermöglichen<br />

die Schalter mit Bimetallauslösern einen<br />

einwandfreien Anlauf des Motors. Als<br />

Schutz vor dem Kurzschluss muss man in<br />

die Zuleitungen vor den Schaltern träge<br />

Sicherungen einsetzen.<br />

• Motorschutzschalter ist eine Einrichtung,<br />

die dazu dient, den Motor ein- und<br />

ausschalten und ihn gleichzeitig zu<br />

schützen. In dem Schalter sind Bimetallrelais<br />

für den Schutz gegen Überlastung und<br />

elektromagnetische Schnellauslöser zum<br />

Schutz gegen Kurzschluss eingebaut.<br />

Die Motorschutzschalter können auch<br />

mit einem Unterspannungsauslöser<br />

ausgerüstet werden, welcher im Falle<br />

des Netzspannungsabfalls auf 50% des<br />

Nennspannungswertes oder völligen<br />

Spannungsausfalls den Motor vom Netz<br />

abtrennt. Der Unterspannungsauslöser<br />

schaltet gleichzeitig auch den<br />

Motorschutzschalter aus. Nach dem<br />

Verschwinden der Ursache für das<br />

Ausschalten des Schalters, muss man<br />

ihn wieder per Handdruck auf den Taster<br />

einschalten.<br />

37

Hurra! Ihre Datei wurde hochgeladen und ist bereit für die Veröffentlichung.

Erfolgreich gespeichert!

Leider ist etwas schief gelaufen!