Appendix G Setup More Modbus RTU Salve Ports<br />

The XP-8xx7-CE6/XP-8xx6-CE6 can setup up to 9 Modbus RTU slave ports in one<br />

of the COM2/COM3 and in 8 of the COM1, 4~33 (COM6 to COM33 are the<br />

expansion multi-serial ports in slot 1 to 7, refer to the appendix E) .<br />

Note about COM1:<br />

Only the COM1 of XP-8047-CE6/ 8046-CE6 can set up as Modbus RTU slave<br />

port, the COM1 of 3/7 slots models cannot.<br />

1. The first Modbus RTU slave port can be one of the COM2 or COM3 which can<br />

be set via “isaXPce6” setting by mouse (refer to the appendix A.2).<br />

2. Eight of the COM1, 4~33 may be enabled as the 2nd , 3rd , … or 9th Modbus<br />

RTU slave port. (No support other COM port number). Before using this function,<br />

please make sure the above ports do exist and well configured. (refer to the<br />

appendix E)<br />

3. Via 2nd ~ 9th Modbus RTU slave port, user may use ISaGRAF to<br />

Debug/Set_val to the PAC, however user cannot Stop/Download/Update the<br />

ISaGRAF program.<br />

4. To Stop/Download/Update the ISaGRAF program, please use Ethernet port or<br />

the first Modbus RTU slave port (if enabled from one of the COM2 or COM3).<br />

The other slave ports (the 2 nd ~9 th Modbus RTU slave ports if enabled from<br />

COM1,4 ~ 33) are not for ISaGRAF to Stop/Download/Debug.<br />

How to setup ?<br />

1. In the “Programs” windows of the ISaGRAF Workbench, open the “I/O<br />

connection” windows to set up the 2 nd ~ 9 th ports.<br />

Ap-24<br />

Getting Started : The XPAC-8xx7-CE6 PAC, Ver.1.23 , May 2012 by ICP DAS