The fan draws the air through the cooling ducts inside the rectifier cubicle. The exhaust<br />

air is forced into the underfloor space <strong>of</strong> the locomotive.<br />

The rectifier unit has been provided with fuses for protection against over loads. Suitable<br />

signaling and rectifier cubicle fuses are provided to give failure indication both at the driver's Desk.<br />

A damping system comprising <strong>of</strong> capacitors and resistors is installed on the dc side <strong>of</strong><br />

for each bridge. The D.C. damping system is arranged next to the fan on the right side <strong>of</strong> the<br />

cubicle towards the aisle <strong>of</strong> locomotive.<br />

1.4.3 Connection:<br />

Each cubicle contains a Greatz bridge connection ; each <strong>of</strong> 4 arms consists <strong>of</strong> 4 cells<br />

connected in parallel and 3 cells connected in series in case <strong>of</strong> AEG/NGEF/Ruttonsha make and 4<br />

cells in parallel and 4 cells in series in HIRECT Type.<br />

1.4.4 Emergency Operation<br />

In order to permit emergency operation upon failure <strong>of</strong> one or more blowers, a bridging<br />

or changeover switch HVSI is fitted in each cubicle which permits the following types <strong>of</strong> operation:<br />

0 -- Motors and relay switched <strong>of</strong>f.<br />

I -- Motors and relay in operation,<br />

II -- Motors switched <strong>of</strong>f, relay in operation.<br />

III -- Motors switched on, relay in operative.<br />

The following operating procedures are possible for emergency operation :<br />

At position II - One rectifier cubicle is out <strong>of</strong> operation, the supervision <strong>of</strong> the second<br />

cubicle is switched on. The supervision <strong>of</strong> the faulty cubicle is switched on for test purpose.<br />

At position III - Upon failure <strong>of</strong> a blower motor this can be switched <strong>of</strong>f alone via the<br />

switch DMVSI. The second blower can continue to be operated. The blower supervision <strong>of</strong> this<br />

cubicle is then inoperative. However, the second cubicle can be operated at full power.<br />

The switch HVSI has the following additional functions :<br />

and L2.<br />

At position 0 and II - De-energizing the relay Ql18 and switching <strong>of</strong>f the line contactors LI<br />

The position 0 it is thus possible to disconnect one rectifier completely while the<br />

supervision <strong>of</strong> the second rectifier remains in operation.<br />

At position 0 the rectifier cubicles may be tested.<br />

1.4.5 Protective devices<br />

Protection against hole storage effect :- An assembly consisting <strong>of</strong> a capacitor and a resistor<br />

connected in parallel across each cell.<br />

This arrangement prevents dangerous over voltages across the cells which occur upon<br />

cut<strong>of</strong>f <strong>of</strong> the upon commutation.<br />

At the same time, these RC-elements also damp dangerous over-voltage which may be<br />

transmitted to the rectifier via the transformer, should surges occur in the catenary.