) Notch to notch relay Q52 must not be energized<br />
c) The valve ZSMGR must be at normal position.<br />
5.7.2.2 In case <strong>of</strong> auto regression <strong>of</strong> the tap changer GR the relay Q50 is de-energized. The<br />
'down' valve SMGR-VE2 is energized directly by passing BL and MP interlocks.<br />
5.7.2.3 Auto regression also takes place in the event <strong>of</strong> wheel slipping, the action takes place<br />
via line 700 and the closed contact <strong>of</strong> relay Q48. Relay Q48, is energized in the event <strong>of</strong> wheel<br />
slipping through relay QD. In such case slip protection relay Q51 is energized temporarily and<br />
gives supply to down valve SMGR-VE2 till the relay Q48 drops through relay QD after the arrest <strong>of</strong><br />
wheel slip.<br />
5.7.2.4 A down movement <strong>of</strong> the tap changer is interrupted automatically on reaching position<br />
“0” by interruption <strong>of</strong> the feed supply.<br />
5.7.2.5 The relay Q46 supervises the continued running <strong>of</strong> the air motor during regression with<br />
MP on position “0” and thus the return <strong>of</strong> the tap changer to zero.<br />
The following conditions must be satisfied for proper functioning <strong>of</strong> the relays<br />
a) The running braking drum MP must be at position "0"<br />
b) The tap changer must be on position other than zero<br />
c) The handle <strong>of</strong> the valve ZSMGR on the pneumatic control panel must be at the<br />
normal operating position.<br />
Should an air motor stop running with the tap changer away from the zero position and<br />
MP on position “0”, the relay Q46 remains energized and causes the relay Ql18 drop out and open<br />
DJ after 5 seconds,<br />
Any down or up movement <strong>of</strong> the tap changer can be stopped at any time by returning<br />
the master controller to position "N". The tap changer then remains at whatever position has been<br />
reached.<br />
5.7.3 CONTROL BY MASTER CONTROLLER – IMPULSE (+) OR (-)<br />
(Ref. fig. 5.7.2)<br />
The switch positions (+) or (-) are intended for notch by notch up or down movement <strong>of</strong><br />
the tap changer both for running and for braking operation.<br />
The switching sequences and inter relationship correspond to those described under<br />
5.7.2. In addition, the notch to notch relay Q52 goes into action, the feed lines 079 is energized at<br />
position (+) or (-).<br />
At all positions for up or down movement either the up or the down valve is energized.<br />
This energizing will be interrupted by contacts <strong>of</strong> the relay Q52 as soon as the air motor starts<br />
running. The relay Q52, is energized between notches via the contacts 7-8 ASMGR, this state<br />
being maintained via the self holding contacts in the line 079-087. The self holding circuit <strong>of</strong> Q52 is<br />
not cancelled until the master controller handle has been returned to position "N". This<br />
arrangement ensures that the tap changer always moves by only one notch at a time. The<br />
completion <strong>of</strong> the notch to notch movement is assured by the pneumatic control system.