262 Gas Turbine Handbook: Principles and Practices<br />

PLANT CONFIGURATION<br />

The major components of the facility are the gas turbine generator,<br />

the heat recovery steam generator and the steam turbine generator.<br />

(See Figure 16-1).<br />

The gas turbine generator is a General Electric Frame 7EA model<br />

rated at 89 MW. It is a “Quiet Combustor” unit with 10 combustion<br />

cans and 6 fuel nozzles per can. It utilizes steam injection for NO x<br />

control. The turbine is controlled with a G.E. MK IV microprocessor<br />

based control system.<br />

The waste heat from the gas turbine is absorbed by an unfired<br />

heat recovery steam generator (HRSG) provided by Henry Vogt Machine<br />

Co. It has a generating capacity of 292,860 lbs per hour at a<br />

design pressure of 1570 psi and 101,000 lb/hr of 82 psig steam. It has<br />

a boiler surface of 937,000 sf.<br />

The steam turbine is a dual extraction condensing unit manufactured<br />

by AEG Kanis of Nurnberg, Germany. It is rated at 36 MW.<br />

Process steam to the food facility is supplied by controlled extraction<br />

from the turbine during normal operations. Steam for gas turbine<br />

NO x<br />

control is supplied from a 300 psig uncontrolled bleed line.<br />

During periods of plant shutdown for scheduled non-generating<br />

hours and maintenance, steam is supplied by dual auxiliary boilers.<br />

These are Nebraska Boiler Co. products rated at 86,890 lbs. per hour.<br />

They operate at 170 psi and 378 degrees.<br />

The condenser, supplied by Graham Manufacturing, was designed<br />

to maintain feedwater O 2<br />

less than 5 ppb without the use of<br />

a feed water deaerator. Up to 200 gpm of makeup water is scrubbed<br />

of O 2<br />

by the associated vacuum makeup deaerator. The condenser<br />

handles up to 307,000 lb/hr of exhaust steam using 22,000 gpm cooling<br />

water flow.<br />

A Thermal Energy Storage Inlet Air Cooling System was recently<br />

installed to enhance output of the facility during high electrical<br />

demand periods. It is designed to control gas turbine inlet<br />

air temperature at 43 degrees ±1 degree. The system is comprised<br />

of a 750,000-gallon ice storage tank, refrigeration system utilizing<br />

freon-22 and inlet air cooling coils. The system was designed and<br />

constructed under a turnkey contract by Henry Vogt Machine Co.<br />

During off-peak periods, the turbine inlet air is cooled by an<br />

evaporative cooling fogging system supplied by Mee Industries.