Industrial <strong>Application</strong>s<br />
EXPLOSIVE ATMOSPHERES<br />
APPLICATION<br />
INSTALLATION<br />
RECOMMENDED<br />
PRODUCTS<br />
Areas such as munitions depots, grain storage areas, and chemical plants can often<br />
involve explosive atmospheres. It is imperative, therefore, that PIRs used in such<br />
areas contribute no electrical signal or field that could cause ignition.<br />
Mount the 6197 Intrinsically Safe PIR in the hazardous area using either a sealed<br />
cable or sealed conduit fitting. Replace the standard lens with either of the other<br />
two lenses if needed.<br />
Mount the Barrier Box in the non-hazardous area next to the alarm panel.<br />
Run wire between the Barrier Box and the alarm panel terminals. Connect the<br />
ground lug on the bus bar inside the Barrier Box to an intrinsically safe ground<br />
using a 12 AWG wire or larger. Connect the chassis ground on the alarm panel to<br />
earth ground.<br />
Remove the front housing and install the jumpers in the PIR in the walk test<br />
mode. Select either one or two zone mode. Replace the front housing with the<br />
rubber gasket using four screws. Walk test the PIR. Install the Barrier Box lid.<br />
The Sentrol 6197 Intrinsically Safe PIR System is FM-approved and UL Listed<br />
for use in hazardous locations. For non-explosive applications that still require<br />
class I, Division 2, Groups A, B, C & D use the 6198 Non-incendive PIR.<br />
Cable or<br />
Conduit<br />
6197BB (Barrier Box)<br />
Ground Lug<br />
SPACE DETECTION<br />
6197 PIR<br />
+<br />
TAMP<br />
COM<br />
NC<br />
3<br />
4<br />
3<br />
4<br />
3<br />
4<br />
3<br />
4<br />
1<br />
2<br />
3<br />
4<br />
Barriers<br />
12 AWG or larger<br />
Alarm Panel<br />
Switching Module<br />
SUPPLY (RETURN)<br />
+12V<br />
+ SUPPLY (+12V NOM)<br />
Standard Lens Coverage<br />
Top View<br />
40'<br />
12.2m<br />
30'<br />
9.1m<br />
TAMP<br />
TAMP<br />
NC<br />
COM<br />
NO<br />
Cable or<br />
Conduit<br />
Intrinsically Safe<br />
Ground<br />
Earth<br />
Ground<br />
TAMPER LOOP<br />
+ TAMPER LOOP<br />
+ ALARM LOOP<br />
ALARM LOOP<br />
CHASSIS<br />
20'<br />
6.1m<br />
10'<br />
3.0m<br />
0<br />
0 10' 20' 30’ 40'<br />
3.0m 6.1m 9.1m 12.2m<br />
7'<br />
2.1m<br />
0<br />
Side View<br />
4°<br />
30 ° 15° Floor Line<br />
Additonal coverage patterns include vertical barrier and long range.<br />
2.29