MPED-X-Routing-Tender20080721 - Madhya Pradesh State Excise
MPED-X-Routing-Tender20080721 - Madhya Pradesh State Excise
MPED-X-Routing-Tender20080721 - Madhya Pradesh State Excise
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
4.16.a.2) UPS 1 KVA online<br />
1 KVA ONLINE UPS<br />
Requirement<br />
Description<br />
Certifications ISO 9001 & 14001 certified to Manufacturer<br />
Technology Rectifier/Inverter device IGBT based<br />
Full Digital Signal Processing Design<br />
Double Conversion True On-line UPS<br />
Overall efficiency >88% (AC-AC)<br />
Inverter efficiency >90%<br />
Input<br />
Input Voltage & Range 120-280V AC, Single Phase on full load<br />
Input Frequency Range 50 Hz ± 10%<br />
Input Phase<br />
Single Phase with ground<br />
Input current Harmonic THD < 8%<br />
Input Power Factor 0.99 at full load<br />
OUTPUT<br />
Output<br />
1 KVA<br />
Voltage<br />
220VAC<br />
Voltage Regulation +/-2%<br />
Output Frequency regulation Free running Mode 50Hz ± 1%<br />
Sync Mode 50Hz ± 2%<br />
O/p Voltage Distortion < 5% (Non-linear load)<br />
< 2% (linear load)<br />
Output Waveform Pure Sine wave<br />
Crest Factor 3:01<br />
Power Factor<br />
0.7 lagging<br />
Battery<br />
Battery Backup<br />
120 minute<br />
Battery Type<br />
SMF VRLA type only with Racks & Interconnecting Links<br />
Recharing of Battery 4-6 hours depending on depth of discharge of battery<br />
Battery Make<br />
Rocket/Amararaja/Emerson/Exide/Quanta<br />
VDC<br />
To be specified<br />
Battery Ratings<br />
2KVA: 5040VAH<br />
Transfer Time<br />
0 ms<br />
General<br />
Display<br />
LED Display<br />
Overload capacity 105-125%-5 minutes<br />
Operating Temperature 0 to 40 degree centigrade<br />
Noise level<br />