4.16.a.2) UPS 1 KVA online<br />

1 KVA ONLINE UPS<br />

Requirement<br />

Description<br />

Certifications ISO 9001 & 14001 certified to Manufacturer<br />

Technology Rectifier/Inverter device IGBT based<br />

Full Digital Signal Processing Design<br />

Double Conversion True On-line UPS<br />

Overall efficiency >88% (AC-AC)<br />

Inverter efficiency >90%<br />

Input<br />

Input Voltage & Range 120-280V AC, Single Phase on full load<br />

Input Frequency Range 50 Hz ± 10%<br />

Input Phase<br />

Single Phase with ground<br />

Input current Harmonic THD < 8%<br />

Input Power Factor 0.99 at full load<br />

OUTPUT<br />

Output<br />

1 KVA<br />

Voltage<br />

220VAC<br />

Voltage Regulation +/-2%<br />

Output Frequency regulation Free running Mode 50Hz ± 1%<br />

Sync Mode 50Hz ± 2%<br />

O/p Voltage Distortion < 5% (Non-linear load)<br />

< 2% (linear load)<br />

Output Waveform Pure Sine wave<br />

Crest Factor 3:01<br />

Power Factor<br />

0.7 lagging<br />

Battery<br />

Battery Backup<br />

120 minute<br />

Battery Type<br />

SMF VRLA type only with Racks & Interconnecting Links<br />

Recharing of Battery 4-6 hours depending on depth of discharge of battery<br />

Battery Make<br />

Rocket/Amararaja/Emerson/Exide/Quanta<br />

VDC<br />

To be specified<br />

Battery Ratings<br />

2KVA: 5040VAH<br />

Transfer Time<br />

0 ms<br />

General<br />

Display<br />

LED Display<br />

Overload capacity 105-125%-5 minutes<br />

Operating Temperature 0 to 40 degree centigrade<br />

Noise level<br />