Supply, installation, testing and commissioning of True<br />

Online, 1<br />

Double conversion technology 2 X30 KVA UPS ( Input 3<br />

phase, output 3 phase, 415 V) operating in load bus<br />

synchronization mode , harmonic filter & Battery Breaker<br />

with 60 minutes battery back-up<br />

As per BoM<br />

3 Air conditioners<br />

Air conditioner along with power requirement, power<br />

distribution capacity at 21 degree (PEX 130) including floor<br />

insulation, floor grills as required for 600 sq, ft area for 30<br />

KVA heat dissipation and 10 to 15 PCs alongwith 15 to 20<br />

Human Resources.<br />

4 Fire & Security Equipments<br />

As per<br />

Requirement<br />

Siemens or<br />

Equivalent<br />

Fire Alarm Systems 1<br />

FM200 gas based fire protection for the entire data centre<br />

area excluding UPS, staging area & IT support area 1<br />

VESDA 1<br />

5 Repellants & Detection<br />

Rodent Repellant System for server room area 1<br />

Water Leak Detection System 1<br />

6 Electrical works & Power Distribution for powering the<br />

above in dual redundant power supply.<br />

LUMSUM<br />

7 Transient Voltage Surge Suppressors for protection<br />

against Surges/Noise req IT equipments in the Data<br />

Centre<br />

This to connected to the i/p of each UPS System & Air<br />

conditioners with response time 0.5ns & Voltage Protection<br />

Level of < 0.8 KV should be listed with UL-1449-2. The<br />

TVSS shall provide up to 40dB for RFI & EMI noise<br />

attenuation<br />

Liebert or<br />

equivalent<br />

4.34) FM Services for Warranty Period<br />

Network & Systems Management Services<br />

(i) Fault Management<br />

a. Identification and resolution of Network, System, Server<br />

faults.<br />

b. Provide Managed Service using an EMS (Enterprise<br />

Management Software) for network monitoring along with<br />

an application traffic management system that monitors,<br />

controls, and accelerates application performance over the<br />

WAN Internet.<br />

(ii) WAN Management<br />

a. Generate trouble ticket using Helpdesk tool after logging a call<br />

with Lease Line/WAN Link Provider and follow up the same.<br />

84