Supply, installation, testing and commissioning of True<br />
Online, 1<br />
Double conversion technology 2 X30 KVA UPS ( Input 3<br />
phase, output 3 phase, 415 V) operating in load bus<br />
synchronization mode , harmonic filter & Battery Breaker<br />
with 60 minutes battery back-up<br />
As per BoM<br />
3 Air conditioners<br />
Air conditioner along with power requirement, power<br />
distribution capacity at 21 degree (PEX 130) including floor<br />
insulation, floor grills as required for 600 sq, ft area for 30<br />
KVA heat dissipation and 10 to 15 PCs alongwith 15 to 20<br />
Human Resources.<br />
4 Fire & Security Equipments<br />
As per<br />
Requirement<br />
Siemens or<br />
Equivalent<br />
Fire Alarm Systems 1<br />
FM200 gas based fire protection for the entire data centre<br />
area excluding UPS, staging area & IT support area 1<br />
VESDA 1<br />
5 Repellants & Detection<br />
Rodent Repellant System for server room area 1<br />
Water Leak Detection System 1<br />
6 Electrical works & Power Distribution for powering the<br />
above in dual redundant power supply.<br />
LUMSUM<br />
7 Transient Voltage Surge Suppressors for protection<br />
against Surges/Noise req IT equipments in the Data<br />
Centre<br />
This to connected to the i/p of each UPS System & Air<br />
conditioners with response time 0.5ns & Voltage Protection<br />
Level of < 0.8 KV should be listed with UL-1449-2. The<br />
TVSS shall provide up to 40dB for RFI & EMI noise<br />
attenuation<br />
Liebert or<br />
equivalent<br />
4.34) FM Services for Warranty Period<br />
Network & Systems Management Services<br />
(i) Fault Management<br />
a. Identification and resolution of Network, System, Server<br />
faults.<br />
b. Provide Managed Service using an EMS (Enterprise<br />
Management Software) for network monitoring along with<br />
an application traffic management system that monitors,<br />
controls, and accelerates application performance over the<br />
WAN Internet.<br />
(ii) WAN Management<br />
a. Generate trouble ticket using Helpdesk tool after logging a call<br />
with Lease Line/WAN Link Provider and follow up the same.<br />
84