2 Electrical Installation Issue 10/06<br />
Input voltage range 3 AC 500 V – 600 V, ± 10 % (Unfiltered)<br />
Order No.<br />
6SE6<strong>440</strong>- 2UE17-<br />
5CA1<br />
2UE21-<br />
5CA1<br />
2UE22-<br />
2CA1<br />
2UE24-<br />
0CA1<br />
2UE25-<br />
5CA1<br />
2UE27-<br />
5CA1<br />
2UE31-<br />
1CA1<br />
Frame Size C D<br />
Output Rating(CT)<br />
2UE31-<br />
5DA1<br />
[kW] 0,75 1,5 2,2 4,0 5,5 7,5 11,0 15,0<br />
[hp] 1,0 2,0 3,0 5,0 7,5 10,0 15,0 20,0<br />
Output Power [kVA] 1,3 2,6 3,7 5,8 8,6 10,5 16,2 21,0<br />
CT-Input Current 1) [A] 2,0 3,7 5,3 8,1 11,1 14,4 21,5 24,9<br />
CT-Output Current [A] 1,4 2,7 3,9 6,1 9,0 11,0 17,0 22,0<br />
VT-Input Current 1) [A] 3,2 4,4 6,9 9,4 12,6 18,1 24,9 30,0<br />
VT-Output Current [A] 2,7 3,9 6,1 9,0 11,0 17,0 22,0 27,0<br />
Fuse [A] 10 10 10 16 16 25 32 35<br />
Recommended 3NA 3803-6 3803-6 3803-6 3805-6 3805-6 3810-6 3812-6 3814-6<br />
For UL specified 3NE * * * * * * * 1803-0<br />
Input Cable, min.<br />
Input Cable, max.<br />
Output Cable, min.<br />
Output Cable, max.<br />
Weight<br />
[mm 2 ] 1,0 1,0 1,0 1,5 1,5 2,5 4,0 6,0<br />
[AWG] 18 18 18 16 16 14 12 10<br />
[mm 2 ] 10,0 10,0 10,0 10,0 10,0 10,0 10,0 35,0<br />
[AWG] 8 8 8 8 8 8 8 2<br />
[mm 2 ] 1,0 1,0 1,0 1,0 1,0 2,5 4,0 4,0<br />
[AWG] 18 18 18 18 18 14 12 12<br />
[mm 2 ] 10,0 10,0 10,0 10,0 10,0 10,0 10,0 35,0<br />
[AWG] 8 8 8 8 8 8 8 2<br />
[kg] 5,5 5,5 5,5 5,5 5,5 5,5 5,5 16,0<br />
[lbs] 12,1 12,1 12,1 12,1 12,1 12,1 12,1 35,0<br />
Tightening torques for [Nm] 2,25 10<br />
power terminals [lbf.in] (20) (89)<br />
Order No.<br />
6SE6<strong>440</strong>- 2UE31-<br />
8DA1<br />
2UE32-<br />
2DA1<br />
2UE33-<br />
0EA1<br />
2UE33-<br />
7EA1<br />
2UE34-<br />
5FA1<br />
Frame Size D E F<br />
Output Rating(CT)<br />
2UE35-<br />
5FA1<br />
2UE37-<br />
5FA1<br />
[kW] 18,5 22,0 30,0 37,0 45,0 55,0 75,0<br />
[hp] 25,0 30,0 40,0 50,0 60,0 75,0 100,0<br />
Output Power [kVA] 25,7 30,5 39,1 49,5 59,1 73,4 94,3<br />
CT-Input Current 1) [A] 30,0 35,0 48,0 58,0 69,0 83,0 113,0<br />
CT-Output Current [A] 27,0 32,0 41,0 52,0 62,0 77,0 99,0<br />
VT-Input Current 1) [A] 35,0 48,0 58,0 69,0 83,0 113,0 138,0<br />
VT-Output Current [A] 32,0 41,0 52,0 62,0 77,0 99,0 125,0<br />
Fuse [A] 50 63 80 80 125 160 160<br />
Recommended 3NA 3820-6 3822-6 3824-6 3824-6 3132-6 3136-6 3136-6<br />
For UL specified 3NE 1817-0 1818-0 1820-0 1820-0 1022-0 1224-0 1224-0<br />
Input Cable, min.<br />
Input Cable, max.<br />
Output Cable, min.<br />
Output Cable, max.<br />
Weight<br />
[mm 2 ] 10,0 10,0 16,0 25,0 25,0 50,0 50,0<br />
[AWG] 8 8 6 3 3 1/0 1/0<br />
[mm 2 ] 35,0 35,0 35,0 35,0 150,0 150,0 150,0<br />
[AWG] 2 2 2 2 300 300 300<br />
[mm 2 ] 6,0 10,0 16,0 16,0 25,0 35,0 50,0<br />
[AWG] 10 8 6 6 3 2 1/0<br />
[mm 2 ] 35,0 35,0 35,0 35,0 150,0 150,0 150,0<br />
[AWG] 2 2 2 2 300 300 300<br />
[kg] 16,0 16,0 20,0 20,0 56,0 56,0 56,0<br />
[lbs] 35,0 35,0 44,0 44,0 123,0 123,0 123,0<br />
Tightening torques for [Nm] 10 50<br />
power terminals [lbf.in] (89) (445)<br />
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line<br />
supply V k = 2 % referred to the rated drive converter power and a rated line supply voltage<br />
of 500 V without line commutating reactor.<br />
* UL listed fuses such as Class NON from Bussmann are required for use in America<br />
<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />
12 Operating Instructions (Compact)