Issue 10/06<br />

6 Commissioning<br />

6.4.19 Data sets<br />

For many applications it is beneficial to have the possibility to change several<br />

parameter settings simultaneous during operation or in the state ready to run with<br />

an external signal. By indexing it is possible to set a parameter to several values<br />

which can be activated by data set change-over. There are the following data sets:<br />

‣ CDS Command Data Set<br />

‣ DDS Drive Data Set<br />

Command data set (CDS)<br />

P0810 =...<br />

0<br />

Command data set CDS bit 0 (local / remote)<br />

Selects the command source in which bit 0 should be read-out to select a command data<br />

set (CDS).<br />

Selecting CDS<br />

BI: CDS bit 1<br />

P0811<br />

BI: CDS b0 loc/rem<br />

P0810<br />

(0:0)<br />

(0:0)<br />

Active CDS<br />

r0050<br />

3<br />

2<br />

1<br />

0<br />

3<br />

Changeover time<br />

approx. 4 ms<br />

t<br />

Changeover time<br />

approx. 4 ms<br />

CO/BO: Act CtrlWd2<br />

r0055 .15<br />

r0055 .15<br />

CO/BO: Act CtrlWd1<br />

r0054 .15<br />

r0054 .15<br />

2<br />

1<br />

CO: Active CDS<br />

r0050<br />

0<br />

The currently active command data set (CDS) is displayed using parameter r0050.<br />

P0811 =... BI: CDS bit 1<br />

Selects command source from which to read Bit 1 for selecting a command data set<br />

(see P0810).<br />

Example for CDS changeover:<br />

CDS1: Command source via terminals and setpoint source via analog input (ADC)<br />

CDS2: Command source via BOP and setpoint source via MOP<br />

CDS changeover is realized using digital input 4 (DIN 4)<br />

Steps:<br />

1. Carry-out commissioning for CDS1 (P0700[0] = 2 and P1000[0] = 2)<br />

2. Connect P0810 (P0811 if required) to the CDS changeover source<br />

(P0704[0] = 99, P0810 = 722.3)<br />

3. Copy from CDS1 to CDS2 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 2)<br />

4. Adapt CDS2 parameters (P0700[1] = 1 and P1000[1] = 1)<br />

t<br />

DIN4<br />

P0810 = 722.3<br />

Terminals<br />

BOP<br />

P0700[0] = 2<br />

P0700[1] = 1<br />

0<br />

1<br />

Sequence control<br />

ADC<br />

MOP<br />

P1000[0] = 2<br />

P1000[1] = 1<br />

0<br />

1<br />

Setpoint<br />

channel<br />

Motor<br />

control<br />

<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />

Operating Instructions (Compact) 69