4 Communications Issue 10/06<br />
4 Communications<br />
4.1 Establishing communications<br />
<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong> ⇔ STARTER<br />
The following optional components are additionally required in order to establish<br />
communications between STARTER and <strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong>:<br />
‣ PC frequency inverter connecting set<br />
‣ BOP if the USS standard values (refer to Section 6.4.1 "Serial Interface (USS)")<br />
are changed in the <strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong> frequency inverter<br />
PC frequency inverter connecting set <strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />
USS settings, refer to 6.4.1 "Serial<br />
Interface (USS)"<br />
STARTER<br />
Menu, Options --> Set PG/PC interface<br />
--> Select "PC COM-Port (USS)" --><br />
Properties --> Interface "COM1", select<br />
a baud rate<br />
NOTE<br />
The USS parameter settings in the<br />
<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong> frequency inverter<br />
and the settings in STARTER must<br />
match!<br />
4.2 Establishing communications<br />
<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong> ⇔ AOP<br />
‣ Communications between AOP and MM<strong>440</strong> are based on the USS protocol,<br />
analog to STARTER and MM<strong>440</strong>.<br />
‣ Contrary to the BOP, the appropriate communication parameters - both for the<br />
MM<strong>440</strong> as well as for AOP - should be set if the automatic interface detection<br />
was not carried-out (refer to Table 4-1).<br />
‣ Using the optional components, the AOP can be connected to the<br />
communication interfaces (refer to Table 4-1).<br />
Table 4-1<br />
MM<strong>440</strong> parameters<br />
- baud rate<br />
- bus address<br />
AOP parameters<br />
- baud rate<br />
- bus address<br />
Options<br />
- direct connection<br />
- indirect connection<br />
AOP at the BOP link<br />
P2010[1]<br />
–<br />
P8553<br />
–<br />
No option necessary<br />
BOP/AOP door mounting kit<br />
(6SE6400-0PM00-0AA0)<br />
AOP at the COM link<br />
P2010[0]<br />
P2011<br />
P8553<br />
P8552<br />
Not possible<br />
AOP door mounting kit<br />
(6SE6400-0MD00-0AA0)<br />
<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />
24 Operating Instructions (Compact)