Issue 10/06<br />

6 Commissioning<br />

r0054 CO/BO: Control word 1<br />

Displays the first control word (STW) of the frequency inverter and can be used to display<br />

the active commands.<br />

Bit00 ON/OFF1 0 NO 1 YES<br />

Bit01 OFF2: Electrical stop 0 YES 1 NO<br />

Bit02 OFF3: Fast stop 0 YES 1 NO<br />

Bit03 Pulse enable 0 NO 1 YES<br />

Bit04 RFG enable 0 NO 1 YES<br />

Bit05 RFG start 0 NO 1 YES<br />

Bit06 Setpoint enable 0 NO 1 YES<br />

Bit07 Fault acknowledge 0 NO 1 YES<br />

Bit08 JOG right 0 NO 1 YES<br />

Bit09 JOG left 0 NO 1 YES<br />

Bit10 Control from PLC 0 NO 1 YES<br />

Bit11 Reverse (setpoint inversion) 0 NO 1 YES<br />

Bit13 Motor potentiometer MOP up 0 NO 1 YES<br />

Bit14 Motor potentiometer MOP down 0 NO 1 YES<br />

Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES<br />

r0063<br />

CO: Actual frequency<br />

Displays the actual frequency in Hz.<br />

Frequency actual values:<br />

60<br />

r0313<br />

Smoothed speed act. value<br />

V/f<br />

160 ms<br />

r0022<br />

P1300<br />

Smoothed freq. actual value<br />

r0021<br />

SLVC<br />

(observer<br />

model)<br />

Encoder<br />

r0313<br />

60 ⋅P0408<br />

0<br />

P0400<br />

0<br />

1,2<br />

F0090<br />

r0067<br />

CO: Act. output current limit<br />

Displays valid maximum output current of inverter.<br />

P0305<br />

Motor<br />

Inverter<br />

P0640<br />

Motor protection<br />

r0209<br />

Inverter protection<br />

Min<br />

r0067<br />

r0072<br />

CO: Act. output voltage<br />

Displays output voltage.<br />