Issue 10/06<br />
6 Commissioning<br />
r0054 CO/BO: Control word 1<br />
Displays the first control word (STW) of the frequency inverter and can be used to display<br />
the active commands.<br />
Bit00 ON/OFF1 0 NO 1 YES<br />
Bit01 OFF2: Electrical stop 0 YES 1 NO<br />
Bit02 OFF3: Fast stop 0 YES 1 NO<br />
Bit03 Pulse enable 0 NO 1 YES<br />
Bit04 RFG enable 0 NO 1 YES<br />
Bit05 RFG start 0 NO 1 YES<br />
Bit06 Setpoint enable 0 NO 1 YES<br />
Bit07 Fault acknowledge 0 NO 1 YES<br />
Bit08 JOG right 0 NO 1 YES<br />
Bit09 JOG left 0 NO 1 YES<br />
Bit10 Control from PLC 0 NO 1 YES<br />
Bit11 Reverse (setpoint inversion) 0 NO 1 YES<br />
Bit13 Motor potentiometer MOP up 0 NO 1 YES<br />
Bit14 Motor potentiometer MOP down 0 NO 1 YES<br />
Bit15 CDS Bit 0 (Local/Remote) 0 NO 1 YES<br />
r0063<br />
CO: Actual frequency<br />
Displays the actual frequency in Hz.<br />
Frequency actual values:<br />
60<br />
r0313<br />
Smoothed speed act. value<br />
V/f<br />
160 ms<br />
r0022<br />
P1300<br />
Smoothed freq. actual value<br />
r0021<br />
SLVC<br />
(observer<br />
model)<br />
Encoder<br />
r0313<br />
60 ⋅P0408<br />
0<br />
P0400<br />
0<br />
1,2<br />
F0090<br />
r0067<br />
CO: Act. output current limit<br />
Displays valid maximum output current of inverter.<br />
P0305<br />
Motor<br />
Inverter<br />
P0640<br />
Motor protection<br />
r0209<br />
Inverter protection<br />
Min<br />
r0067<br />
r0072<br />
CO: Act. output voltage<br />
Displays output voltage.<br />
<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />
Operating Instructions (Compact) 73