6 Commissioning<br />

6.4.18.11 Free function blocks (FFB)<br />

P2800 =...<br />

P2801 =...<br />

P2802 =...<br />

Enable FFBs<br />

0<br />

Parameter P2800 is used to activate all free function blocks (generally, P2800 is set to 1).<br />

Possible settings:<br />

0 Inhibited<br />

1 Enabled<br />

Activate FFBs<br />

0.0<br />

Parameter P2801 is used to individually enable (activate) the free function blocks P2801[0]<br />

to P2801[16] (P2801[x] > 0).<br />

Further, parameters P2801 and P2802 are used to define the chronological sequence of<br />

all of the function blocks. The table below indicates that the priority increases from left to<br />

right and from bottom to top.<br />

Possible settings:<br />

0 Inactive<br />

1 Level 1<br />

2 Level 2<br />

3 Level 3<br />

Example:<br />

P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2<br />

FFBs are calculated in the following sequence:<br />

P2802[3], P2801[3] , P2801[4], P2802[4]<br />

The active function blocks are calculated every 132 ms.<br />

Activate FFBs<br />

Parameter P2802 is used to individually enable (activate) the free function blocks P2802[0]<br />

to P2802[13] (P2802[x] > 0).<br />

Possible settings:<br />

0 Inactive<br />

1 Level 1<br />

2 Level 2<br />

3 Level 3<br />

Level 3<br />

Level 2<br />

Level 1<br />

Inactive 0<br />

low<br />

Priority 2<br />

high<br />

Priority 1<br />

P2802 [13] CMP 2<br />

P2802 [12] CMP 1<br />

P2802 [11] DIV 2<br />

P2802 [10] DIV 1<br />

P2802 [9] MUL 2<br />

P2802 [8] MUL 1<br />

P2802 [7] SUB 2<br />

P2802 [6] SUB 1<br />

P2802 [5] ADD 2<br />

P2802 [4] ADD 1<br />

P2802 [3] Timer 4<br />

P2802 [2] Timer 3<br />

P2802 [1] Timer 2<br />

P2802 [0] Timer 1<br />

P2801 [16] RS-FF 3<br />

P2801 [15] RS-FF 2<br />

P2801 [14] RS-FF 1<br />

P2801 [13] D-FF 2<br />

P2801 [12] D-FF 1<br />

P2801 [11] NOT 3<br />

P2801 [10] NOT 2<br />

P2801 [9] NOT 1<br />

P2801 [8] XOR 3<br />

P2801 [7] XOR 2<br />

P2801 [6] XOR 1<br />

P2801 [5] OR 3<br />

P2801 [4] OR 2<br />

P2801 [3] OR 1<br />

P2801 [2] AND 3<br />

P2801 [1] AND 2<br />

P2801 [0] AND 1<br />

low<br />

<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />

Operating Instructions (Compact) 67