6 Commissioning Issue 10/06<br />

6.4.18.4 DC brake<br />

P1230 = ...<br />

BI: Enabling the DC brake<br />

This enables DC braking using a signal that was used from an external source. The<br />

function remains active as long as the external input signal is active. DC braking causes<br />

the motor to quickly stop by injecting a DC current<br />

BI: Enable DC brk.<br />

P1230.C 1<br />

(0:0)<br />

0<br />

⏐f⏐<br />

f*<br />

DC braking<br />

f_set<br />

t<br />

f_act<br />

i<br />

P0347<br />

t<br />

DC braking active<br />

t<br />

r0053<br />

Bit00<br />

1<br />

0<br />

t<br />

Note: DC brake can be applied in drive states r0002 = 1, 4, 5<br />

P1232 =...<br />

P1233 =...<br />

DC braking current (entered in %)<br />

Defines level of DC current in [%] relative to rated motor current (P0305).<br />

100 %<br />

Duration of DC braking (entered in s)<br />

0 s<br />

Defines duration for which DC injection braking is to be active following an OFF1 or OFF3<br />

command.<br />

1<br />

ON<br />

OFF1/OFF3<br />

OFF2<br />

P0347<br />

t<br />

t<br />

⏐f⏐<br />

P1234<br />

OFF2<br />

DC braking<br />

DC braking active<br />

t<br />

r0053<br />

Bit00<br />

1<br />

0<br />

P1233<br />

t<br />

<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />

58 Operating Instructions (Compact)