6 Commissioning Issue 10/06<br />

6.4.6 Analog input (ADC)<br />

P0756 = ...<br />

ADC type<br />

Defines the analog input type and activates the monitoring<br />

function of the analog input.<br />

0<br />

0 Unipolar voltage input (0 to +10 V)<br />

1 Unipolar voltage input with monitoring ADC1<br />

(0 to 10 V)<br />

2 Unipolar current input (0 to 20 mA)<br />

3 Unipolar current input with monitoring<br />

(0 to 20 mA)<br />

4 Bipolar voltage input (-10 to +10 V)<br />

NOTE<br />

For P0756 to P0760, the following applies:<br />

Index 0 : Analog input 1 (ADC1), terminals 3, 4<br />

Index 1 : Analog input 2 (ADC2), terminals 10, 11<br />

OFF = [V], 0 - 10 V<br />

ON = [A], 0 - 20 mA<br />

ADC2<br />

OFF = [V], 0 - 10 V<br />

ON = [A], 0 - 20 mA<br />

7<br />

P0757 =...<br />

P0758 =...<br />

P0759 =...<br />

Value x1 of ADC scaling<br />

0 V<br />

Value y1 of ADC scaling 0.0 %<br />

This parameter represents the<br />

value of x1 as a % of P2000<br />

(reference frequency).<br />

Value x2 of ADC scaling 10 V<br />

P0761 > 0<br />

0 < P0758 < P0760 || 0 > P0758 > P0760<br />

%<br />

100 %<br />

4000 h<br />

<strong>AS</strong>Pmax<br />

P0760<br />

P0760 =...<br />

P0761 =...<br />

Value y2 of ADC scaling 100.0 %<br />

This parameter represents the<br />

value of x2 as a % of P2000<br />

(reference frequency).<br />

Width of ADC deadband 0 V<br />

Defines width of deadband on<br />

analog input.<br />

P0758<br />

<strong>AS</strong>Pmin<br />

P0761<br />

P0757<br />

P0757 = P0761<br />

P0759<br />

10 V<br />

20 mA<br />

x 100%<br />

V<br />

mA<br />

P0762 = ...<br />

Delay, ADC signal loss<br />

10 ms<br />

Defines the delay time between the loss of the analog setpoint and fault message F0080<br />

being displayed.<br />

ADC channel<br />

KL3<br />

ADC+<br />

KL4<br />

ADC−<br />

DIP switch<br />

ADC<br />

type<br />

A<br />

D<br />

P0756<br />

ADC<br />

type<br />

P0753<br />

P0757<br />

P0758<br />

P0759<br />

P0760<br />

ADC<br />

scaling<br />

r0754<br />

P0761<br />

ADC<br />

dead<br />

zone<br />

P1000<br />

r0755<br />

Setpoint<br />

Pxxxx<br />

P0756<br />

P0761<br />

P0762<br />

r0752<br />

Wire<br />

breakage<br />

sensing<br />

1 1.7 V 0<br />

3.9 V P0707<br />

T 0<br />

r0722<br />

r0722.6<br />

Pxxxx<br />

F0080<br />

r0751<br />

Function<br />