29.12.2014 Views

MICROMASTER 440 - Siemens AS

MICROMASTER 440 - Siemens AS

MICROMASTER 440 - Siemens AS

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Issue 10/06<br />

6 Commissioning<br />

Example:<br />

1. Commissioning steps with a motor:<br />

− Carry-out commissioning at DDS1.<br />

− Connect P0820 (P0821 if required) to the DDS changeover source<br />

(e.g. using DIN 4: P0704[0] = 99, P0820 = 722.3).<br />

− Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2).<br />

− Adapt DDS2 parameters<br />

(e.g. ramp-up / ramp-down times P1120[1] and P1121[1]).<br />

DIN<br />

Sequence control<br />

ADC<br />

SUM<br />

setpoint<br />

AFM<br />

RFG<br />

Motor<br />

control<br />

Gating unit<br />

M<br />

P0820 = 722.3<br />

DIN4<br />

0 1<br />

P1120<br />

P1121<br />

[0]<br />

DDS1<br />

[1]<br />

DDS2<br />

[2]<br />

DDS3<br />

2. Commissioning steps with 2 motors (motor 1, motor 2):<br />

− Commission motor 1; adapt the remaining DDS1 parameters.<br />

− Connect P0820 (P0821 if required) to the DDS changeover source<br />

(e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3).<br />

− Changeover to DDS2 (check using r0051).<br />

− Commission motor 2; adapt the remaining DDS2 parameters.<br />

M1<br />

Motor 1<br />

MM4<br />

K1<br />

M2<br />

Motor 2<br />

K2<br />

<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />

Operating Instructions (Compact) 71