Issue 10/06<br />
6 Commissioning<br />
Example:<br />
1. Commissioning steps with a motor:<br />
− Carry-out commissioning at DDS1.<br />
− Connect P0820 (P0821 if required) to the DDS changeover source<br />
(e.g. using DIN 4: P0704[0] = 99, P0820 = 722.3).<br />
− Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2).<br />
− Adapt DDS2 parameters<br />
(e.g. ramp-up / ramp-down times P1120[1] and P1121[1]).<br />
DIN<br />
Sequence control<br />
ADC<br />
SUM<br />
setpoint<br />
AFM<br />
RFG<br />
Motor<br />
control<br />
Gating unit<br />
M<br />
P0820 = 722.3<br />
DIN4<br />
0 1<br />
P1120<br />
P1121<br />
[0]<br />
DDS1<br />
[1]<br />
DDS2<br />
[2]<br />
DDS3<br />
2. Commissioning steps with 2 motors (motor 1, motor 2):<br />
− Commission motor 1; adapt the remaining DDS1 parameters.<br />
− Connect P0820 (P0821 if required) to the DDS changeover source<br />
(e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3).<br />
− Changeover to DDS2 (check using r0051).<br />
− Commission motor 2; adapt the remaining DDS2 parameters.<br />
M1<br />
Motor 1<br />
MM4<br />
K1<br />
M2<br />
Motor 2<br />
K2<br />
<strong>MICROM<strong>AS</strong>TER</strong> <strong>440</strong><br />
Operating Instructions (Compact) 71