Input/Output <strong>Instructions</strong> (MSG, GSV, SSV, IOT) 193Attribute Data Type Instruction DescriptionPendingBaudRate DINT SSV Pending value for the BaudRate attribute.PendingDataBits SINT SSV Pending value for the DataBits attribute.PendingParity SINT SSV Pending value for the Parity attribute.PendingRTSOffDelay INT SSV Pending value for the RTSOffDelay attribute.PendingRTSSendDelay INT SSV Pending value for the RTSSendDelay attribute.PendingStopBits SINT SSV Pending value for the StopBits attribute.To apply values for any of the SERIALPORT pending attributes:1. Use an SSV instruction to set the value for the pending attribute.You can set as many pending attributes as you want, using anSSV instruction for each pending attribute.2. Use a MSG instruction to apply the value. The MSG instructionapplies every pending attribute you set. Configure the MSGinstructions as:MSG Configuration Tab Field ValueConfiguration Message Type CIP GenericService Code0d hexObject Type6f hexObject ID 1Object Attributeleave blankSourceleave blankNumber of Elements 0Destinationleave blankCommunication Path communication path to self(1,s where s = slot number ofcontroller)Publication 1756-RM003I-EN-P - January 2007