Special <strong>Instructions</strong> (FBC, DDT, DTR, PID) 497Enter an immediate mask valueWhen you enter a mask, the programming software defaults todecimal values. If you want to enter a mask using another format,precede the value with the correct prefix.PrefixDescription:16# hexadecimalfor example; 16#0F0F8# octalfor example; 8#162# binaryfor example; 2#00110011Arithmetic Status Flags:Fault Conditions:not affectednoneExecution:Conditionprescanrung-condition-in is falseRelay Ladder ActionThe Reference = Source AND Mask.The rung-condition-out is set to false.The Reference = Source AND Mask.The rung-condition-out is set to false.rung-condition-in is truemasked source =referencenoreference is set equal to masked sourcerung-condition-out is set to trueyesrung-condition-out is setto falseendpostscanThe rung-condition-out is set to false.Publication 1756-RM003I-EN-P - January 2007