Compare <strong>Instructions</strong> (CMP, EQU, GEQ, GRT, LEQ, LES, LIM, MEQ, NEQ) 225Function BlockOperand Type Format DescriptionLEQ tag FBD_COMPARE structure LEQ structureFBD_COMPARE StructureInput Parameter Data Type DescriptionEnableIn BOOL Enable input. If cleared, the instruction does not execute and outputs are not updated.Default is set.SourceA REAL Value to test against SourceB.Valid = any floatSourceB REAL Value to test against SourceA.Valid = any floatOutput Parameter Data Type DescriptionEnableOut BOOL The instruction produced a valid result.Dest BOOL Result of the instruction. This is equivalent to rung-condition-out for the relay ladderLEQ instruction.Description:The LEQ instruction tests whether Source A is less than or equal toSource B.When you compare strings:• The hexadecimal values of the characters determine if one stringis less than or greater than another string. For the hex code of acharacter, see the back cover of this manual.• When the two strings are sorted as in a telephone directory, theorder of the strings determines which one is greater.ASCII CharactersHex Codes1ab $31$61$62lessergreater1b $31$62A $41AB $41$42B $42a $61AB < Ba > Bab $61$62Publication 1756-RM003I-EN-P - January 2007