74 Bit <strong>Instructions</strong> (XIC, XIO, OTE, OTL, OTU, ONS, OSR, OSF, OSRI, OSFI)Output Energize (OTE)The OTE instruction sets or clears the data bit.Operands:Relay LadderOperand Type Format Descriptiondata bit BOOL tag bit to be set or clearedStructured TextStructured text does not have an OTE instruction, but you can achievethe same results using a non-retentive assignment.data_bit [:=] BOOL_expression;See Appendix B for information on the syntax of assignments andexpressions within structured text.Description:Arithmetic Status Flags:Fault Conditions:When the OTE instruction is enabled, the controller sets the data bit.When the OTE instruction is disabled, the controller clears thedata bit.not affectednoneExecution:Conditionprescanrung-condition-in is falserung-condition-in is truepostscanRelay Ladder ActionThe data bit is cleared.The rung-condition-out is set to false.The data bit is cleared.The rung-condition-out is set to false.The data bit is set.The rung-condition-out is set to true.The data bit is cleared.The rung-condition-out is set to false.Publication 1756-RM003I-EN-P - January 2007