408 Array (File)/Shift <strong>Instructions</strong> (BSL, BSR, FFL, FFU, LFL, LFU)LIFO Load (LFL)The LFL instruction copies the Source value to the LIFO.Operands:Relay LadderOperand Type Format DescriptionSource SINT immediate data to be stored in the LIFOINTtagDINTREALstringLIFOstructureThe Source converts to the data type of the array tag. A smaller integerconverts to a larger integer by sign-extension.SINTarray tagLIFO to modifyINTDINTspecify the first element of the LIFOdo not use CONTROL.POS in the subscriptREALstringstructureControl CONTROL tag control structure for the operationtypically use the same CONTROL as theassociated LFULength DINT immediate maximum number of elements the LIFO canhold at one timePosition DINT immediate next location in the LIFO where theinstruction loads datainitial value is typically 0If you use a user-defined structure as the data type for the Source orLIFO operand, use the same structure for both operands.Publication 1756-RM003I-EN-P - January 2007