ASCII Serial Port <strong>Instructions</strong> (ABL, ACB, ACL, AHL, ARD, ARL, AWA, AWT) 573The following timing diagram depicts the changes in the status bits asan ABL instruction tests the buffer for termination characters.scan scan scan scanrung-condition-in false true false true false.EN off on off on off.EU off on.RN off on off on off.DN or .ER off on off on.FD off on off on.EM off on off onenters queueresets status bitsexecutesin this example,finds terminationcharacterswhen scanned and .DNor .ER are set, sets the.EM bitThe ASCII queue holds up to 16 instructions. When the queue is full,an instruction tries to enter the queue on each subsequent scan of theinstruction, as depicted below:scan scan scan scanrung-condition-in false true false.EN off on.EU off onattempts to enter queue but queue is fullenters queuePublication 1756-RM003I-EN-P - January 2007