440 Program Control <strong>Instructions</strong> (JMP, LBL, JSR, RET, SBR, JXR, TND, MCR, UID, UIE, AFI, NOP, EOT, SFP, SFR, EVENT)ATTENTIONFor each parameter in a SBR or RET instruction, use the samedata type (including any array dimensions) as the correspondingparameter in the JSR instruction. Using different data typesmay produce unexpected results.SBR Operands:The SBR instruction must be the first instruction in a relay ladder orstructured text routine.Relay LadderOperand Type Format DescriptionInputparameterBOOLSINTINTDINTREALstructuretagarray tagtag in this routine into which you want tocopy the corresponding input parameter fromthe JSR instructionSBR(InputPar);Structured TextThe operands are the same as those for the relay ladderSBR instruction.Function BlockParametersgThe operands are the same as those for the relay ladderSBR instruction.Publication 1756-RM003I-EN-P - January 2007