9.7.7. Sensor Disconnection Detection Control<br />

• The sensor disconnection detection control activates when the following condition comply:<br />

Sensor Detection Threshold Duration (Sec.) Detection Condition<br />

Discharge Temperature < -4.5°C or 201.8°C 5 Other than compressor start control<br />

and compressor ON<br />

Outdoor Heat Exchanger < -50.5°C or 103.7°C 5 Regularly<br />

• During sensor disconnection, sensor error is displayed; all operations stops except outdoor fan remaining heat removal control.<br />

9.7.8. High-pressure Switch Disconnection Error Detection Control<br />

• High-pressure switch disconnection is detected when high-pressure switch input continuously open for 1 minutes while the compressor<br />

shutdown.<br />

• During this error, high-pressure switch error is displayed.<br />

9.7.9. Low-pressure Switch Disconnection Error Detection Control<br />

• Low-pressure switch disconnection is detected when low-pressure switch input continuously open for 1 minutes while compressor<br />

shutdown.<br />

• During this error, low-pressure switch error is displayed.<br />

9.8. Test Run<br />

• Test run is necessary after installation is completed.<br />

• To enable forced cooling test run, at outdoor PCB, set the DS1 to position below:<br />

• To enable forced heating test run, at outdoor PCB, set the DS1 to position below:<br />

• Press Test Run button at outdoor pcb for 1 second.<br />

29