10.5.12. As to making the inspection after completion of work fully understood<br />

• At the time when the work has been completed, measure and record the characteristics of test run without fail and keep the measuring<br />

date, etc.<br />

• Carry out the measurement regarding room temperature outside air temperature, suction and air discharge temperatures, wind<br />

velocity, wind volume, voltage current, presence of abnormal vibration, operating pressure, piping temperature, compressive<br />

pressure, airtight pressure as items to be measured.<br />

• As to the structure and appearance, check following items.<br />

Short circuit of the blow-out air<br />

Smooth flow of the drain<br />

Reliable thermal insulation<br />

Leakage of refrigerant<br />

Mistake in wiring<br />

10.5.13. As to delivery to the customer<br />

• Request the customer to operate this air conditioner viewing instruction manual come with indoor unit in practice and explain<br />

how to operate.<br />

• Deliver the instruction manual to the customer without fail.<br />

53<br />

Reliable connection of the grand wire<br />

Looseness in terminal screw, fastening torque<br />

M3... 69-98N•cm {7-10kgf•cm} M4... 157-196N.cm {16-20kgf•cm}<br />

M5... 196-245N•cm {20-25kgf•cm}