10.6.5. Test operation<br />

• Turn on the main power.<br />

• After 3 minutes have passed since the power was turned on, press the OFF/ON switch on the remote controller. (No operation occurs within 3<br />

minutes after the power was turned on.)<br />

• Press the TEST RUN switch within 1 minute of pressing the OFF/ON switch.<br />

• Next, select the operation mode. (Be sure to select cooling mode first, and run the unit in this mode for 5 minutes<br />

or more.)<br />

• Press the OFF/ON switch or the TEST RUN switch to cancel test operation.<br />

• Test operation will be cancelled automatically after 30 minutes.<br />

• Check once more that the remote control cable is securely connected. (Check for loose terminals, poor contacts, connection<br />

positions terminal block, etc.)<br />

• If the above checks show that nothing is wrong but nothing appears on the remote controller display.<br />

• It is possible that the remote controller was connected while the main power was still turned on. If such is the case, carry out the<br />

following.<br />

• Set DIP switch (SW2) No. 1 to 4. The ON position, and then turn on the main power. If the display appears after about 30 seconds,<br />

turn DIP switches 2 to 4 to OFF position.<br />

10.6.6. Self-diagnosis function<br />

If remote controller displays nothing<br />

If “CHECK” is blinking on the timer<br />

• If the “CHECK” display on the wired remote controller is blinking, the details of the problems are displayed on the timer display<br />

screen each time the CHECK switch is pressed.<br />

• Further details of the problem can be displayed by pressing the SET switch while the general problem details are being displayed.<br />

Example of current problem display<br />

If “CHECK” is not blinking on the timer<br />

• If the “CHECK” display on the wired remote controller is not blinking, press the CHECK switch continuously for 5 seconds or<br />

more to display the problem details for the last problem or the problem before that.<br />

• You can then switch between the display for the previous problem and the problem before that by pressing the UP (TIMER)<br />

DOWN (TIMER) switches.<br />

• Press the CHECK switch once more to return to the normal display.<br />