12 Troubleshooting Guide<br />

If test operation does not proceed correctly<br />

Carry out test operation after approximately 12 hours have passed since the power was turned on (crankcase heater is energized). If<br />

operation is started by using the remote control within 1 minute of turning on the power, the outdoor unit settings will not be made correctly<br />

and correct operation will not be possible.<br />

If the following symptoms occur after turning on the power, check the wiring connections once more.<br />

12.1. For standard installation<br />

System example<br />

1. The main power is turned on while the indoor-outdoor transmission wires are not connected.<br />

(open circuit at A: power line)<br />

Symptom<br />

Indoor unit: no power supply<br />

Remote control unit: no power supply<br />

Outdoor unit: LED2, 4, 6 on P.C.B flashes<br />

2. The main power is turned on while the indoor-outdoor transmission wires are not connected.<br />

(open circuit at B: power/transmission line)<br />

Symptom<br />

Indoor unit: no power supply<br />

Remote control unit: no power supply<br />

Outdoor unit: LED2, 4, 6 on P.C.B flashes<br />

3. The main power is turned on while the indoor-outdoor transmission wires are not connected.<br />

(open circuit at C: transmission line)<br />

Symptom<br />

Remote control unit: “check” flashes<br />

Error code: F27-01 (indoor/outdoor transmission error)<br />

Indoor unit: LED1 on P.C.B flashes<br />

Outdoor unit: LED2, 4, 6 on P.C.B flashes<br />