4. Refrigerant filling<br />

Refrigerant filling must be done in the state of liquid refrigerant. If this is done in gas refrigerant, the balance of refrigerant<br />

composition will collapse and damage the operation.<br />

For the use of a gas cylinder without siphon inside, turn it upside down and use it.<br />

(We recommend manifold with sight glass.)<br />

Caution Do not use a “CHARGE CYLINDER”.<br />

Caution As a rule, please collect all existing refrigerants in the system outside the system when the refrigerant leakage occurs by the<br />

system.<br />

After that, please fill new refrigerant of a regulated amount again.<br />

DRY VACUUMING<br />

• If vacuum pump possible vacuuming until less than -100.7kpa.<br />

1. Running vacuum pump at both liquid and gas side for more than 1 hour and vacuuming until -100.7kpa.<br />

2. After that keep the pressure -100.7kpa for 1 hour and confirm the vacuum gauge value not increasing.<br />

3. If vacuum gauge value is increase, there is possibility of water inside the unit or there is any leakage.<br />

10.5.3. Regarding handling<br />

Handling the unit by hold the handle at compressor side and hold the basepan bottom at fan side.<br />

10.5.4. Selecting the outdoor unit installation locations<br />

• Select location which satisfies the following condition, and then confirm with the customer that such a place is satisfactory before<br />

installing the outdoor unit.<br />

1. There should be sufficient ventilation.<br />

2. The outdoor unit should be sheltered as much as possible from rain and direct sunlight, and the air should be able to move around so that hot<br />