10.5.7. Heat insulation<br />

10.5.8. Charging with refrigerant<br />

1.5 HP • 2 HP (14 • 18 type)<br />

• At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 20m. If the<br />

equivalent pipe length used will be 20m or less, no additional charging will be necessary.<br />

• If the equivalent pipe length will be between 20 and 30m, charge with additional refrigerant according to the equivalent length<br />

given in the table below.<br />

2.5 HP ~ 6 HP (24 ~ 50 type)<br />

• At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30m. If the<br />

equivalent pipe length used will be 30m or less, no additional charging will be necessary.<br />

• If the equivalent pipe length will be between 30 and 50m, charge with additional refrigerant according to the equivalent length<br />

given in the table below.<br />

• Pump down operation<br />

- Operate the pump down according to the following procedures.<br />

10.5.9. Electrical wiring<br />

Caution<br />

Use a material with good heat-resistant properties as the<br />

heat insulation for the pipes. Be sure to insulate both the<br />

gas-side and liquid-side pipes. If the pipes are not adequately<br />

insulated, condensation or water leakages may<br />

occur.<br />

Liquid-side pipes Material that can withstand<br />

Gas-side pipes 120°C or higher<br />

Model Additional charging amount Equivalent length<br />

1.5 HP • 2 HP (14 • 18 type) 0.02 kg/m 30m<br />

2.5 HP ~ 6 HP (24 ~ 50 type) 0.05 kg/m 50m<br />

Procedure Notes<br />

1. Confirm the valve on the liquid side and the gas side is surely open.<br />

2. Press the PUMP DOWN switch on outdoor printed board for 1 second Perform the cooling operation for five minutes or more.<br />

or more.<br />

3. Shut the valve on the liquid side surely. When the valve is shut halfway, the compressor is occasionally damaged.<br />

The units must be connected to the supply cables for fixed wiring by qualified technician.<br />

Feed the power source to the unit via a distribution switch board designed for this purpose, the switch should disconnected all<br />

poles with a contact separation of at least 3mm.<br />

When the supply cable is damaged, it must be replaced by qualified technician.<br />

Warning Be sure to install a current leakage breaker, main switch and fuse to the main power supply, otherwise electric shocks may result.<br />

Be sure to connect the unit to secure earth connection.<br />

If the earthing work is not carried out properly, electric shocks may result.<br />

Wiring shall be connected securely by using specified cables and fix them securely so that external force of the cables may not<br />

transfer to the terminal connection section.<br />

Imperfect connection and fixing leads to fire, etc.<br />

• Connect the power supply wiring and indoor/outdoor unit connection wiring according to the electrical circuit diagram instructions.<br />

• Clamp the wires securely to the terminal connections using cord clamps so that no undue force is placed on the wires.<br />

• Once all wiring work has been completed, tie the wires and cords together with the binding strap so that they do not touch other<br />

parts such as the compressor and pipes.<br />

49