1.4. Operation range<br />

1.4.1. Power Supply<br />

The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be balanced<br />

within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the<br />

rated voltage.<br />

MODEL Unit Main Power Applicable Voltage<br />

CU- Phase, Volts Hz Max. Min.<br />

1 ~ 220 50 242 198<br />

J18DBE5 1 ~ 230 50 253 207<br />

1 ~ 240 50 264 216<br />

1.4.2. Indoor and Outdoor Temperature<br />

• Model 50Hz CU-J18DBE5<br />

Operating Hz Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C)<br />

Max. Min. Max. Min.<br />

Cooling 50 32/23 21/15 43/- -5/-<br />