• Power supply specifications<br />

Model name<br />

Leakage<br />

current<br />

breaker<br />

10.5.10. Connecting power supply cables<br />

Circuit breaker<br />

(Minimum Capacity) Minimum<br />

power<br />

CAUTION<br />

• For three phase model, never operate the unit by pressing the electromagnetic switch.<br />

• Never correct the phase by switching over any of the wires inside the unit.<br />

(A)<br />

Switch<br />

(A)<br />

51<br />

Fuse<br />

(A)<br />

supply<br />

cables<br />

4mm2 cable<br />

based on<br />

length (m)<br />

Maximum<br />

permissible<br />

impedance<br />

(Ω)<br />

CU-B14DBE5 CU-J14DBE5 220V-240V~ 15 15 15 35 0.0374<br />

CU-B18DBE8 CU-J18DBE8 220V-240V~ 20 20 20 24 0.0374<br />

CU-B24DBE5 CU-J24DBE5 220V-240V~ 30 30 20<br />

4 mm2 16 0.0374<br />

CU-B24DBE8 CU-J24DBE8 380V-415V 3N~ 15 15 15 68 0.1017<br />

CU-B28DBE5 CU-J28DBE5 220V-240V~ 30 30 30 16 0.0374<br />

CU-B28DBE8 CU-J28DBE8 380V-415V 3N~ 15 15 15 59 0.1017<br />

CU-B34DBE5 CU-J34DBE5 220V-240V~ 40 40 40 10 0.0374<br />

CU-B34DBE8 CU-J34DBE8 380V-415V 3N~ 20 20 20 38 0.1017<br />

CU-B43DBE8 CU-J43DBE8 380V-415V 3N~ 20 20 20 27 0.1017<br />

CU-B50DBE8 CU-J50DBE8 380V-415V 3N~ 20 20 20 25 0.1017<br />

NOTE<br />

Indoor/outdoor<br />

unit connection<br />

power cables<br />

(terminals ,<br />

, , )<br />

2.5 mm 2 × 4<br />

1. Where ground work (earth) is carried out, do not connect the ground return to the gas pipe, water line pipe, grounded circuit of the<br />

telephone and lightning rod, or ground circuit of other product in which earth leakage breaker is incorporated. (Such action is prohibited<br />

by statute, etc.)<br />

Make sure the indoor and outdoor connection wires are detangled. (There might be effect to received outside noise.)<br />

2. Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR) rating specifications)<br />

or use the cables based on IEC standard. (245IEC57, 245IEC66)<br />

3. Select the particular size of electrical wire for power supply cables in accordance with the standards of the given nation and region.