• Power supply specifications<br />
Model name<br />
Leakage<br />
current<br />
breaker<br />
10.5.10. Connecting power supply cables<br />
Circuit breaker<br />
(Minimum Capacity) Minimum<br />
power<br />
CAUTION<br />
• For three phase model, never operate the unit by pressing the electromagnetic switch.<br />
• Never correct the phase by switching over any of the wires inside the unit.<br />
(A)<br />
Switch<br />
(A)<br />
51<br />
Fuse<br />
(A)<br />
supply<br />
cables<br />
4mm2 cable<br />
based on<br />
length (m)<br />
Maximum<br />
permissible<br />
impedance<br />
(Ω)<br />
CU-B14DBE5 CU-J14DBE5 220V-240V~ 15 15 15 35 0.0374<br />
CU-B18DBE8 CU-J18DBE8 220V-240V~ 20 20 20 24 0.0374<br />
CU-B24DBE5 CU-J24DBE5 220V-240V~ 30 30 20<br />
4 mm2 16 0.0374<br />
CU-B24DBE8 CU-J24DBE8 380V-415V 3N~ 15 15 15 68 0.1017<br />
CU-B28DBE5 CU-J28DBE5 220V-240V~ 30 30 30 16 0.0374<br />
CU-B28DBE8 CU-J28DBE8 380V-415V 3N~ 15 15 15 59 0.1017<br />
CU-B34DBE5 CU-J34DBE5 220V-240V~ 40 40 40 10 0.0374<br />
CU-B34DBE8 CU-J34DBE8 380V-415V 3N~ 20 20 20 38 0.1017<br />
CU-B43DBE8 CU-J43DBE8 380V-415V 3N~ 20 20 20 27 0.1017<br />
CU-B50DBE8 CU-J50DBE8 380V-415V 3N~ 20 20 20 25 0.1017<br />
NOTE<br />
Indoor/outdoor<br />
unit connection<br />
power cables<br />
(terminals ,<br />
, , )<br />
2.5 mm 2 × 4<br />
1. Where ground work (earth) is carried out, do not connect the ground return to the gas pipe, water line pipe, grounded circuit of the<br />
telephone and lightning rod, or ground circuit of other product in which earth leakage breaker is incorporated. (Such action is prohibited<br />
by statute, etc.)<br />
Make sure the indoor and outdoor connection wires are detangled. (There might be effect to received outside noise.)<br />
2. Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR) rating specifications)<br />
or use the cables based on IEC standard. (245IEC57, 245IEC66)<br />
3. Select the particular size of electrical wire for power supply cables in accordance with the standards of the given nation and region.